Summary
The Beckhoff TS6509 is an Industrial/Embedded PC running the TwinCAT IEC 61850/IEC 61400-25 Server, providing a Server-Client communication interface over MMS (Manufacturing Message Specification) mapped onto TCP/IP (COTP, ISO 8073, port 102). This spec covers the implemented IEC 61850-7-2 ACSI services, supported MMS services, and the PLC function-block actions exposed by the TcIEC61850Server library.
Transport
protocols:
- tcp
addressing:
port: 102 # COTP (ISO 8073), stated in ST_MMS_ProtocolPara.nPort default and firewall table
auth:
type: optional # source: bAccessCtrl default FALSE (disabled), configurable per-user password auth via ST_MMS_AccessControl
notes: |
Authentication is configurable. When bAccessCtrl=TRUE the server validates each
association against ST_MMS_AccessControl entries (authentMechanism '2.2.3.1' =
joint-isoccitt.2.3.1 = 52 03 01 hex; default password 'PASSWORD',
MAX_MMS_PASSWORD_LENGTH=10). When FALSE, no authentication is performed.
Traits
# - queryable # inferred: GetDataValues / GetAllDataValues / read query commands present
traits:
- queryable
Actions
# IEC 61850-7-2 ACSI services marked Implemented = Y in the interoperability checklist.
# Each is a distinct row in the source "Client/server services supported" table.
- id: get_server_directory
label: GetServerDirectory
kind: query
command: "GetServerDirectory"
params: []
- id: associate
label: Associate
kind: action
command: "Associate"
params: []
- id: abort
label: Abort
kind: action
command: "Abort"
params: []
- id: release
label: Release
kind: action
command: "Release"
params: []
- id: get_logical_device_directory
label: GetLogicalDeviceDirectory
kind: query
command: "GetLogicalDeviceDirectory"
params: []
- id: get_logical_node_directory
label: GetLogicalNodeDirectory
kind: query
command: "GetLogicalNodeDirectory"
params: []
- id: get_all_data_values
label: GetAllDataValues
kind: query
command: "GetAllDataValues"
params: []
- id: get_data_values
label: GetDataValues
kind: query
command: "GetDataValues"
params: []
- id: set_data_values
label: SetDataValues
kind: action
command: "SetDataValues"
params: []
- id: get_data_directory
label: GetDataDirectory
kind: query
command: "GetDataDirectory"
params: []
- id: get_data_definition
label: GetDataDefinition
kind: query
command: "GetDataDefinition"
params: []
- id: create_data_set
label: CreateDataSet
kind: action
command: "CreateDataSet"
params: []
- id: delete_data_set
label: DeleteDataSet
kind: action
command: "DeleteDataSet"
params: []
- id: get_data_set_directory
label: GetDataSetDirectory
kind: query
command: "GetDataSetDirectory"
params: []
# MMS services marked Server-CR = Y in the "MMS conformance" table.
# Distinct rows in source; not collapsed with ACSI equivalents.
- id: mms_get_name_list
label: MMS getNameList
kind: query
command: "getNameList"
params: []
- id: mms_identify
label: MMS identify
kind: query
command: "identify"
params: []
- id: mms_read
label: MMS read
kind: query
command: "read"
params: []
- id: mms_write
label: MMS write
kind: action
command: "write"
params: []
- id: mms_get_variable_access_attributes
label: MMS getVariableAccessAttributes
kind: query
command: "getVariableAccessAttributes"
params: []
- id: mms_define_named_variable_list
label: MMS defineNamedVariableList
kind: action
command: "defineNamedVariableList"
params: []
- id: mms_get_named_variable_list_attributes
label: MMS getNamedVariableListAttributes
kind: query
command: "getNamedVariableListAttributes"
params: []
- id: mms_delete_named_variable_list
label: MMS deleteNamedVariableList
kind: action
command: "deleteNamedVariableList"
params: []
- id: mms_conclude
label: MMS conclude
kind: action
command: "conclude"
params: []
# PLC function-block (FB_IEC61850Server) actions. These are TwinCAT PLC-side
# state transitions, not wire commands, but the source documents them as the
# two discrete actions of the server block.
- id: plc_a_init
label: FB_IEC61850Server A_INIT
kind: action
command: "A_INIT"
params: []
notes: "Transitions server IDLE -> INITIALIZING -> PREOP; initializes internal IEC 61850 object database."
- id: plc_a_operate
label: FB_IEC61850Server A_OPERATE
kind: action
command: "A_OPERATE"
params: []
notes: "Transitions server PREOP -> OPERATIONAL; enables client connections and active data exchange."
# NOTE on UNRESOLVED payloads: The source is an IEC 61850/MMS server library
# manual. ACSI/MMS services are protocol service primitives whose on-wire
# encoding is ASN.1 BER (TcASN1.Lib) and is NOT given verbatim in this source.
# The literal hex byte payloads for each service are therefore UNRESOLVED;
# only the service/primitive names are documented here.
Feedbacks
- id: ied_state
type: enum
description: "Server operating state (E_IED_State output of FB_IEC61850Server.eState)"
values:
- eIED_STATE_IDLE # 0
- eIED_STATE_INITIALIZING
- eIED_STATE_PREOP
- eIED_STATE_OPERATIONAL
- eIED_STATE_STOPPING
- id: mms_environment
type: enum
description: "MMS runtime environment status (E_MMS_Environment)"
values:
- eMMS_Environment_None # 0, inactive
- eMMS_Environment_Establishing
- eMMS_Environment_Running
- eMMS_Environment_Relinquishing
- id: authenticated_user
type: boolean
description: "ST_MMS_ApplicationAssociation.bAuthentUser - TRUE if association used an authentication password."
Variables
- id: max_pdu_size
type: integer
description: "ST_MMS_ApplicationPara.maxPDUsize - max byte length of the PDU (default 65000)."
- id: max_serv_out_calling
type: integer
description: "maxServOutCalling - max authorised unconfirmed MMS services at the calling system (default 10)."
- id: max_serv_out_called
type: integer
description: "maxServOutCalled - max authorised unconfirmed MMS services at the called system (default 10)."
- id: nesting_level
type: integer
description: "max interlacing depth of MMS object data (default 5)."
- id: tpdu_size
type: enum
description: "E_COTP_DUsize - max byte length of transport layer data segment (default eCOTP_DUsize_1024 = 1024 byte)."
values: [128, 256, 512, 1024, 2048, 4096, 8192, 16384, 32768]
- id: local_host
type: string
description: "ST_MMS_ProtocolPara.sHost - local IPv4 server host address (default '127.0.0.1')."
- id: keepalive_time_ms
type: integer
description: "OS-level TCP KeepAliveTime (default 2 hours = 7200000 ms). OS registry setting, not a TwinCAT setting."
- id: keepalive_interval_ms
type: integer
description: "OS-level TCP KeepAliveInterval (default 1 second = 1000 ms). OS registry setting, not a TwinCAT setting."
Events
# UNRESOLVED: source does not document unsolicited notification payloads.
# Report Control Block (Report / GetBRCBValues / GetURCBValues) and GOOSE publish
# services are marked N* (in development) / N in the interoperability checklist,
# so no unsolicited event emission is fully specified by this source.
Macros
# UNRESOLVED: source documents no multi-step command sequences as macros.
# The example program in section 5.1.1.1 shows an init->operate PLC sequence but
# is application code, not a device-defined macro.
Safety
confirmation_required_for: []
interlocks: []
# UNRESOLVED: source contains no safety warnings, interlock procedures, or
# power-on sequencing requirements. IEC 61850 Control services (Select,
# SelectWithValue, Operate, Cancel, CommandTermination, TimeActivatedOperate)
# are all marked NOT implemented (N) in the interoperability checklist, so no
# control-command interlock semantics are specified by this source.
Notes
- The TS6509 here functions as an IEC 61850/61400-25 server (publisher of a data model), not a conventional AV switcher/display. "Commands" are MMS/ACSI service primitives plus two TwinCAT PLC function-block actions (
A_INIT,A_OPERATE). - Transport stack (top to bottom): ACSI (TcACSI.Lib) -> MMS (TcMMS.Lib) -> ASN.1 BER (TcASN1.Lib) -> TwinCAT TCP/IP Connection Server -> COTP (ISO 8073) -> TCP port 102.
- MMS conformance: only the Server role is realized (Client-CR column is entirely N). Supported CBB params: STR1, STR2, VNAM, VALT, TPY, VLIS. Not supported: VADR, VSCA, REAL, CEI.
- GOOSE is partially supported (receive side, "Only GOOSE, not GSE Management") but all GOOSE conformance rows are marked N in the statement, so GOOSE control-block access is not exposed.
- Maximum coexistent Application-Associations = 1 (
MAX_MMS_APPLICATION_ASSOCIATIONS); maximum user accounts = 4 (MAX_MMS_ACCESS_CONTROL_USERS). - ACSI service errors are enumerated in
E_ACSI_ServiceError(0x0000 success through 0x850B). - TCP keep-alive values are OS-level registry settings (Windows W2K/XP/Embedded Standard and Windows CE paths given in Appendix 7.1), not TwinCAT configuration.
Provenance
source_domains:
- download.beckhoff.com
- infosys.beckhoff.com
source_urls:
- https://download.beckhoff.com/download/Document/automation/twincat2/TS6509_TcPlcLibIEC61400_25Server_en.pdf
- https://infosys.beckhoff.com/content/1033/tcplclibiec61400_25server/11681610507.html
retrieved_at: 2026-08-04T18:08:13.196Z
last_checked_at: 2026-08-05T08:07:27.749Z
Verification Summary
verdict: verified
checked_at: 2026-08-05T08:07:27.749Z
matched_actions: 25
action_count: 25
confidence: medium
summary: "All 25 spec actions map to ACSE/MMS services marked Y in the source conformance tables, plus the two PLC FB actions A_INIT and A_OPERATE. (7 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "hardware voltage/current/power specs not stated in source. Exact PDU/session negotiation values are defaults configurable at deployment; only library defaults are documented."
- "source does not document unsolicited notification payloads."
- "source documents no multi-step command sequences as macros."
- "source contains no safety warnings, interlock procedures, or"
- "firmware/hardware revision compatibility not stated (source references TwinCAT v2.10.0 Build >= 1340 as the PLC library build, not device firmware)."
- "literal ASN.1 BER hex encodings for each MMS/ACSI service not provided in this source."
- "hardware power/voltage/current specifications not present in source."