Summary
The Somfy URTSI II is an RS-485 transmitter that speaks the Somfy Digital Network (SDN) protocol for controlling Somfy motorized window-covering devices. This spec covers the SDN bus protocol exposed by the URTSI II: bus configuration, frame structure, and the full set of SET / CTRL / GET / POST / ACK / NACK message opcodes documented for the bus.
Transport
# URTSI II exposes an RS-485 differential serial bus running the SDN protocol.
# All data bytes are logically inverted before transmission (complement of each byte).
protocols:
- serial
serial:
baud_rate: 4800
data_bits: 8
parity: odd
stop_bits: 1
flow_control: none
# UNRESOLVED: source documents "Start Bit = logical level 0" and "Stop Bit = logical level 1" but not flow control; assumed none
auth:
type: none # inferred: no auth procedure in source
Frame structure (per §5 of source): every SDN frame is 11–32 bytes, laid out as MSG | ACK/LEN | NODE_TYPE | SOURCE@ (3 bytes) | DEST@ (3 bytes) | DATA (0–21 bytes) | CHECKSUM. The checksum is the sum of bytes 1 through n-2 (no error correction). No sync byte; frame end is detected by bus inactivity. SOURCE@ and DEST@ are LSB-first. The actions below document the MSG opcode and DATA payload for each command; the surrounding frame fields (SOURCE@, DEST@, ACK bit, CHECKSUM) must be wrapped by the controller per §5.
Traits
# Source documents explicit query/GET opcodes that elicit POST responses, plus
# status POSTs that the device emits. Power-on/off is implicit via the SDN bus
# (e.g. NETWORK_LOCK save/restore on power cycle) but not a discrete command.
- queryable # inferred from GET_/POST_ opcode pairs and unsolicited status reports
Actions
# Every distinct opcode documented in the SDN source. Each SET/GET/POST/ACK/NACK
# is one action. The `command` field is the literal MSG opcode (hex) from the
# source; DATA layout is described via `params` and inline notes.
# --- Device Management: NodeID ---
- id: get_node_addr
label: Get Node Address
kind: query
command: "40h"
params: []
notes: |
MASTER → bus. SLAVE replies with POST_NODE_ADDR (60h) carrying its
3-byte NodeID in the message header. With many devices on the bus,
not all replies are guaranteed.
- id: post_node_addr
label: Post Node Address
kind: event
command: "60h"
params: []
notes: |
SLAVE → MASTER. Unsolicited report in response to GET_NODE_ADDR.
NodeID is in the SOURCE@/DEST@ header, no DATA bytes.
# --- Device Management: Group Configuration ---
- id: set_group_addr
label: Set Group Address
kind: action
command: "51h"
params:
- name: group_index
type: integer
description: Entry in the group table (0-15)
- name: group_id
type: integer
description: 24-bit GroupID (LSB-first)
notes: DATA length = 4 bytes: GroupIndex (8 bits) + GroupID (24 bits).
- id: get_group_addr
label: Get Group Address
kind: query
command: "41h"
params:
- name: group_index
type: integer
description: Entry in the group table (0-15)
notes: DATA length = 1 byte (GroupIndex). Slave replies with POST_GROUP_ADDR.
- id: post_group_addr
label: Post Group Address
kind: event
command: "61h"
params: []
notes: |
DATA length = 4 bytes: GroupIndex (8 bits) + GroupID (24 bits, n/a).
Reply to GET_GROUP_ADDR.
# --- Acknowledgement and Errors ---
- id: ack
label: Acknowledgement
kind: event
command: "7Fh"
params: []
notes: |
Slave → master. Sent only when the request had the ACK bit set
(CTRL, GET, or SET). Confirms settings saved or control execution
started (not necessarily finished).
- id: nack
label: Negative Acknowledgement
kind: event
command: "6Fh"
params:
- name: error_code
type: integer
description: |
8-bit error code: 01h = Data out of range; 10h = Unknown message;
11h = Message length error; FFh = Busy.
notes: DATA length = 1 byte (ErrorCode).
# --- Device Information: Firmware Revision ---
- id: get_node_app_version
label: Get Firmware Revision
kind: query
command: "74h"
params: []
notes: Slave replies with POST_NODE_APP_VERSION.
- id: post_node_app_version
label: Post Firmware Revision
kind: event
command: "75h"
params: []
notes: |
DATA length = 6 bytes: App_Reference (24 bits, firmware part number),
App_IndexLetter (8 bits ASCII, 41h-5Ah = major rev),
App_IndexNumber (8 bits, firmware rev), Reserved (8 bits).
Example: 5063486A02 is coded 4Dh 43h 3Eh | 41h | 02h.
# --- Device Information: User-defined Text Label ---
- id: set_node_label
label: Set Node Label
kind: action
command: "55h"
params:
- name: label
type: string
description: 16-character text label; pad with spaces if shorter
notes: DATA length = 16 bytes (always).
- id: get_node_label
label: Get Node Label
kind: query
command: "45h"
params: []
notes: Slave replies with POST_NODE_LABEL.
- id: post_node_label
label: Post Node Label
kind: event
command: "65h"
params:
- name: label
type: string
description: 16-character text label
notes: DATA length = 16 bytes. Reply to GET_NODE_LABEL.
# --- Device Configuration: HMI Management ---
- id: set_local_ui
label: Set HMI (Local UI) Lock
kind: action
command: "17h"
params:
- name: function
type: integer
description: 00h = Enable/Unlock, 01h = Disable/Lock
- name: ui_index
type: integer
description: |
00h = All local controls and feedbacks; 01h = DCT input;
02h = Local stimuli (e.g. radio pairing pushbutton);
03h = Local radio access (e.g. Bluetooth);
04h = Touch Motion feature; 05h = LEDs
- name: priority
type: integer
description: 00h-FFh, greater = higher priority lock
notes: |
DATA length = 3 bytes. For UI_Index=00h, priority must be ≥ the
highest existing lock level or NACK(LOW_PRIORITY) is returned.
DCT / Local Stimuli lock state is NOT saved across power cycles;
all other items are saved and restored.
- id: get_local_ui
label: Get HMI (Local UI) Status
kind: query
command: "27h"
params:
- name: ui_index
type: integer
description: 01h-UI_MAX (see SET_LOCAL_UI for indices)
notes: DATA length = 1 byte (UI_Index). Slave replies with POST_LOCAL_UI.
- id: post_local_ui
label: Post HMI (Local UI) Status
kind: event
command: "37h"
params: []
notes: |
DATA length = 5 bytes: UI_Index (8 bits), Status (00h=Enabled,
01h=Disabled), Source_Addr (24-bit, who set the lock),
Priority (8 bits). When unlocked, Source_Addr=000000h, Priority=00h.
# --- Device Configuration: Intermediate Positions ---
- id: set_motor_ip
label: Set Intermediate Position
kind: action
command: "15h"
params:
- name: function
type: integer
description: |
00h = Delete IP (Value ignored; NACK if IP not set);
01h = Set IP at current position (Value ignored);
03h = Set IP at specified position in % (Value = %);
04h = Divide full range into N IPs (Value = count, IP_Index ignored)
- name: ip_index
type: integer
description: 1-16, which intermediate position slot
- name: value
type: integer
description: 16-bit; meaning depends on Function (ignored, % position, or IP count)
notes: |
DATA length = 4 bytes: Function (8) + IP_Index (8) + Value (16).
Function 04h example: Value=2 sets IP1=33%, IP2=66%;
Value=3 sets IP1=25%, IP2=50%, IP3=75%. Existing IPs are overwritten.
- id: get_motor_ip
label: Get Intermediate Position
kind: query
command: "25h"
params:
- name: ip_index
type: integer
description: 1-16
notes: DATA length = 1 byte. Slave replies with POST_MOTOR_IP.
- id: post_motor_ip
label: Post Intermediate Position
kind: event
command: "35h"
params: []
notes: |
DATA length = 4 bytes: IP_index (8), Reserved (16),
IP_position_percentage (8, 0-100, FFh if IP not set).
Reply to GET_MOTOR_IP.
# --- Device Configuration: Speed Adjustment (DC motors only) ---
- id: set_motor_rolling_speed
label: Set Motor Rolling Speed
kind: action
command: "13h"
params:
- name: up_speed
type: integer
description: 8-bit speed (rpm) during UP movement; range per motor datasheet
- name: down_speed
type: integer
description: 8-bit speed (rpm) during DOWN movement; range per motor datasheet
- name: slow_speed
type: integer
description: 8-bit speed (rpm) for adjustment movements; range per motor datasheet
notes: |
DATA length = 3 bytes. Default and range are motor-specific;
see device technical datasheet. Only supported on DC motors.
- id: get_motor_rolling_speed
label: Get Motor Rolling Speed
kind: query
command: "23h"
params: []
notes: DATA length = 0. Slave replies with POST_MOTOR_ROLLING_SPEED.
- id: post_motor_rolling_speed
label: Post Motor Rolling Speed
kind: event
command: "33h"
params: []
notes: |
DATA length = 3 bytes: UP_Speed (8), DOWN_Speed (8), Slow_Speed (8).
Ranges per motor datasheet.
# --- Device Configuration: Lock Network Commands ---
- id: set_network_lock
label: Set Network Lock
kind: action
command: "16h"
params:
- name: function
type: integer
description: |
00h = Unlock (Priority applied); 01h = Lock at current position;
03h = Save NETWORK_LOCK across power cycles (Priority ignored);
04h = Do not save NETWORK_LOCK across power cycles (Priority ignored)
- name: priority
type: integer
description: 00h-FFh, greater = higher priority
notes: |
DATA length = 2 bytes. When locked, only CTRL_MOVETO with equal or
higher priority is accepted; all other movement/limit messages
return NACK(NODE_IS_LOCKED). Factory default = Do Not Save.
- id: get_network_lock
label: Get Network Lock Status
kind: query
command: "26h"
params: []
notes: DATA length = 0. Slave replies with POST_NETWORK_LOCK.
- id: post_network_lock
label: Post Network Lock Status
kind: event
command: "36h"
params: []
notes: |
DATA length = 6 bytes: Status (00h=Unlocked, 01h=Locked),
Source_Addr (24-bit, who locked), Priority (8 bits),
Saved (00h=not restored on power cycle, 01h=restored).
When unlocked, Source_Addr=000000h and Priority=00h.
# --- Device Control: Move to Position ---
- id: ctrl_moveto
label: Move To Position
kind: action
command: "03h"
params:
- name: function
type: integer
description: |
00h = Move to DOWN limit (Position ignored);
01h = Move to UP limit (Position ignored);
02h = Move to Intermediate Position (Position = IP index 0-15);
04h = Move to Position in % of full travel (Position = 0-100)
- name: position
type: integer
description: 16-bit; meaning depends on Function
- name: reserved
type: integer
description: 8-bit reserved (00h)
notes: DATA length = 4 bytes: Function (8) + Position (16) + Reserved (8).
# --- Device Control: Stop ---
- id: ctrl_stop
label: Stop
kind: action
command: "02h"
params:
- name: reserved
type: integer
description: 8-bit reserved
notes: |
DATA length = 1 byte. Motor stops immediately, no speed ramp-down.
# --- Device Status: Motor Position ---
- id: get_motor_position
label: Get Motor Position
kind: query
command: "0Ch"
params: []
notes: Slave replies with POST_MOTOR_POSITION. Position is reported even while running.
- id: post_motor_position
label: Post Motor Position
kind: event
command: "0Dh"
params: []
notes: |
DATA length = 5 bytes: Position_pulse (16, UP_LIMIT-DOWN_LIMIT),
Position_percentage (8, 0-100), Reserved (8), IP (8, 01h-IP_MAX,
FFh = not at an IP).
# --- Device Status: Motor Status ---
- id: get_motor_status
label: Get Motor Status
kind: query
command: "0Eh"
params: []
notes: Slave replies with POST_MOTOR_STATUS.
- id: post_motor_status
label: Post Motor Status
kind: event
command: "0Fh"
params: []
notes: |
DATA length = 4 bytes:
Status (8): 00h=Stopped, 01h=Running, 02h=Blocked (thermal/obstacle), 03h=Locked;
Direction (8): 00h=Going DOWN, 01h=Going UP, FFh=Unknown;
Source (8): 00h=Internal, 01h=Network message, 02h=Local UI;
Cause (8): 00h=Target reached, 01h=Explicit command, 02h=Wink,
20h=Obstacle detection, 21h=Over-current protection,
22h=Thermal protection, 30h=Run time exceeded,
32h=Timeout exceeded (>2 min on CTRL_MOVE), FFh=Reset/PowerUp.
Feedbacks
- id: node_address
type: integer
description: 24-bit NodeID reported in POST_NODE_ADDR header.
- id: group_address
type: integer
description: 24-bit GroupID reported in POST_GROUP_ADDR.
- id: firmware_part_number
type: integer
description: 24-bit App_Reference from POST_NODE_APP_VERSION.
- id: firmware_index_letter
type: string
description: ASCII byte (41h-5Ah) for firmware major revision.
- id: firmware_index_number
type: integer
description: 8-bit firmware revision index.
- id: node_label
type: string
description: 16-character user-defined label from POST_NODE_LABEL.
- id: local_ui_status
type: enum
values: [enabled_unlocked, disabled_locked]
description: Per-UI_Index status from POST_LOCAL_UI; Source_Addr and Priority identify locker.
- id: motor_ip_position
type: integer
description: 0-100 percentage for a given IP_index; FFh means IP not set.
- id: motor_speed_up
type: integer
description: 8-bit UP speed (rpm) from POST_MOTOR_ROLLING_SPEED.
- id: motor_speed_down
type: integer
description: 8-bit DOWN speed (rpm).
- id: motor_speed_slow
type: integer
description: 8-bit slow/adjustment speed (rpm).
- id: network_lock_status
type: enum
values: [unlocked, locked]
description: From POST_NETWORK_LOCK.
- id: network_lock_saved
type: enum
values: [not_restored_on_power_cycle, restored_on_power_cycle]
- id: motor_position_pulse
type: integer
description: 16-bit pulse count (UP_LIMIT-DOWN_LIMIT).
- id: motor_position_percentage
type: integer
description: 0-100 percent of full travel range.
- id: motor_position_ip
type: integer
description: 1-IP_MAX (matching IP index) or FFh if not at an IP.
- id: motor_status
type: enum
values: [stopped, running, blocked, locked]
- id: motor_direction
type: enum
values: [going_down, going_up, unknown]
- id: motor_command_source
type: enum
values: [internal, network_message, local_ui]
- id: motor_status_cause
type: enum
values: [target_reached, explicit_command, wink, obstacle_detection, over_current_protection, thermal_protection, run_time_exceeded, timeout_exceeded, reset_powerup]
- id: nack_error_code
type: enum
values: [data_out_of_range, unknown_message, message_length_error, busy]
description: Error code byte from NACK (6Fh).
Variables
# Settable, non-discrete parameters the source exposes via SET opcodes.
- id: group_address
type: integer
description: 24-bit GroupID; settable via SET_GROUP_ADDR per GroupIndex 0-15.
- id: node_label
type: string
description: 16-character label; settable via SET_NODE_LABEL.
- id: local_ui_lock_function
type: enum
values: [enable_unlock, disable_lock]
description: SET_LOCAL_UI Function byte.
- id: local_ui_lock_priority
type: integer
description: 00h-FFh priority for the HMI lock; greater = higher.
- id: motor_ip_index
type: integer
description: IP slot 1-16.
- id: motor_ip_value
type: integer
description: Position (0-100) or IP count, interpretation depends on Function.
- id: motor_speed_up
type: integer
description: UP speed (rpm); range per motor datasheet.
- id: motor_speed_down
type: integer
description: DOWN speed (rpm); range per motor datasheet.
- id: motor_speed_slow
type: integer
description: Slow/adjustment speed (rpm); range per motor datasheet.
- id: network_lock_function
type: enum
values: [unlock, lock, save_across_power_cycle, do_not_save_across_power_cycle]
- id: network_lock_priority
type: integer
description: 00h-FFh; ignored for Functions 03h and 04h.
Events
# Unsolicited notifications from the URTSI II / downstream SDN nodes.
- id: post_node_addr
opcode: "60h"
description: Reply to GET_NODE_ADDR; carries 3-byte NodeID in header.
- id: post_group_addr
opcode: "61h"
description: Reply to GET_GROUP_ADDR.
- id: post_node_app_version
opcode: "75h"
description: Firmware version report.
- id: post_node_label
opcode: "65h"
description: 16-byte label report.
- id: post_local_ui
opcode: "37h"
description: HMI lock status report.
- id: post_motor_ip
opcode: "35h"
description: Intermediate position report.
- id: post_motor_rolling_speed
opcode: "33h"
description: Motor speed report.
- id: post_network_lock
opcode: "36h"
description: Network lock status report.
- id: post_motor_position
opcode: "0Dh"
description: Current motor position; emitted even while running.
- id: post_motor_status
opcode: "0Fh"
description: Motor state / direction / source / cause.
- id: ack
opcode: "7Fh"
description: Sent only when the request's ACK bit was set.
- id: nack
opcode: "6Fh"
description: Error report; carries 1-byte ErrorCode.
Macros
# UNRESOLVED: source does not document multi-step command sequences
Safety
confirmation_required_for: []
interlocks:
- id: network_lock
description: |
When SET_NETWORK_LOCK Function=01h is in effect, all CTRL_xxx movement
commands and SET_MOTOR_LIMITS / SET_TILT_LIMITS messages are rejected
with NACK(NODE_IS_LOCKED) unless they carry equal-or-higher priority.
- id: local_ui_priority
description: |
SET_LOCAL_UI with UI_Index=00h must carry priority ≥ the highest
existing lock level, otherwise NACK(LOW_PRIORITY) is returned.
collision_guidance: |
Avoid requesting feedback or ACK in Group or Broadcast addressing modes
to lower RS-485 collision risk. Use a retry strategy on NACK or on ACK
timeout (Trep range 5-255 ms).
# UNRESOLVED: no electrical, thermal, or mechanical safety warnings stated in source
Notes
- Byte inversion quirk (§4.2): every data byte must be logically inverted (complement) before transmission on the bus. Example: source byte
58his sent on the wire asA7h. The controller must apply the same inversion when receiving. - Frame detection (§4.3): no sync byte. Frame end is implied by bus inactivity exceeding Tfree (3 ms). A master must wait Treq (10 ms) after the last bus activity before transmitting. A slave waits Trep (5–255 ms, partially randomized) before replying. Tc (max 1 ms) must not be exceeded between consecutive characters within a frame.
- Addressing modes (§3.4): Point-to-Point (specific NodeID), Group (SOURCE@=GroupID, DEST@=000000h), Broadcast (DEST@=FFFFFFh), and NodeType filtering (DEST NodeType byte).
- Optional ACK (§3.6, §6.1.3): setting the ACK bit in a SET/CTRL/GET request causes the slave to reply with ACK on success or NACK(ErrorCode) on failure. No ACK follows a status request — the POST_xxx is itself the feedback.
- LOCAL_UI persistence (§6.3.1): DCT and Local Stimuli lock state is NOT saved across power cycles; all other UI locks ARE saved and restored.
- NETWORK_LOCK persistence (§6.3.4): Function 03h saves the highest lock across power cycle, Function 04h does not. Factory default = Do Not Save.
Provenance
source_domains:
- service.somfy.com
source_urls:
- https://service.somfy.com/downloads/bui_v4/sdn-integration-guide--preliminary.pdf
retrieved_at: 2026-04-29T08:47:16.971Z
last_checked_at: 2026-06-02T05:46:21.741Z
Verification Summary
verdict: verified
checked_at: 2026-06-02T05:46:21.741Z
matched_actions: 30
action_count: 30
confidence: medium
summary: "All 30 spec actions matched literally against source opcodes; transport parameters verified from §4.1; 100% coverage. (5 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "source does not state the URTSI II's specific hardware revision, RS-485 termination, or max bus length"
- "source documents \"Start Bit = logical level 0\" and \"Stop Bit = logical level 1\" but not flow control; assumed none"
- "source does not document multi-step command sequences"
- "no electrical, thermal, or mechanical safety warnings stated in source"
- "source refines a generic SDN bus protocol; URTSI II-specific node count, RS-485 termination requirements, max cable length, and exact hardware revision are not stated in source."