Summary

Rako RAV232 (unidirectional) and RAV232+ (bidirectional) are RS-232 RF interfaces for Rako lighting control systems. RAV232 uses 1200 bps and can be switched to 9600 bps with BAUD plus a power cycle; RAV232+ is documented at 9600 bps. The source does not establish BAUD switching for RAV232+. The bidirectional variant receives button-press events from Rako devices. All commands are text-based, case-insensitive, terminated with carriage-return.

The four-page source explicitly covers RAV232 and RAV232+. The similarly named eight-page WRA-232 V2.0.1 document describes a different product and is not used here.

Transport

protocols:
  - serial
serial:
  baud_rate: null  # Select the model/configuration profile below; no single baud rate covers both models.
  data_bits: 8
  parity: none
  stop_bits: 1
  flow_control: none  # Explicitly supported by both models; observe the RAV232+ readiness requirement below.
serial_profiles:
  - model: RAV232
    baud_rates: [1200, 9600]
    flow_control_options: [xon_xoff, none]
    notes: "1200 bps documented configuration. BAUD 96 selects 9600; BAUD 12 selects 1200. Power cycle after selection. 9600 bps requires external power."
  - model: RAV232+
    baud_rates: [9600]
    flow_control_options: [hardware, none]
    notes: "CTS indicates ready to receive. Without CTS, avoid sending too quickly or wait for the > prompt after each command. No numeric pacing interval is documented."
auth:
  type: UNRESOLVED  # Source states neither an authentication procedure nor an explicit absence of authentication.

Traits

- powerable       # OFF command present
- levelable       # LEVEL command present (0-255)
- routable        # HOUSE/ROOM/CHANNEL addressing for multi-device control
- queryable       # STATUS, VER commands present

Actions

- id: house
  label: Set House Address
  kind: action
  command: "HOUSE {house_number}\r"
  params:
    - name: house_number
      type: integer
      min: 1
      max: 255
      description: House address (1-255, stored in non-volatile memory); source warning about HOUSE 0 does not extend this documented setter range.

- id: room
  label: Set Room Address
  kind: action
  command: "ROOM {room_number}\r"
  params:
    - name: room_number
      type: integer
      min: 0
      max: 255
      description: Room address (0-255); 0 = all rooms with matching house; omitted argument selects 0; stored in non-volatile memory.

- id: channel
  label: Set Channel Address
  kind: action
  command: "CHANNEL {channel_number}\r"
  params:
    - name: channel_number
      type: integer
      min: 0
      max: 15
      description: Channel address (0-15); 0 = all channels in current room; omitted argument selects 0.

- id: scene
  label: Set Scene
  kind: action
  command: "SCENE {scene_number}\r"
  params:
    - name: scene_number
      type: integer
      min: 1
      max: 4
      description: Scene number (1-4)

- id: off
  label: Lights Off
  kind: action
  command: "OFF\r"
  params: []

- id: level
  label: Set Power Level
  kind: action
  command: "LEVEL {power_level}\r"
  params:
    - name: power_level
      type: integer
      min: 0
      max: 255
      description: Power level 0-255 (0=0%, 128=50%, 255=100%)

- id: store
  label: Store Scene
  kind: action
  command: "STORE\r"
  description: Stores current power level to the current scene
  params: []

- id: reset
  label: Reset Microcontroller
  kind: action
  command: "RESET\r"
  params: []

- id: command
  label: Send Command Number
  kind: action
  command: "COMMAND {command_number}\r"
  params:
    - name: command_number
      type: integer
      min: 0
      max: 15
      description: Command number (0-15). LIGHT+ and LIGHT- fade lights; STOP halts fade.

- id: address
  label: Set EEPROM Address
  kind: action
  command: "ADDRESS {eeprom_address}\r"
  params:
    - name: eeprom_address
      type: integer
      min: 0
      max: 127
      description: Protocol address domain 0-127; write only documented addresses listed in Notes. Profile addresses 63-127 should only be changed using RASOFT.

- id: data
  label: Write EEPROM Data
  kind: action
  command: "DATA {eeprom_data}\r"
  params:
    - name: eeprom_data
      type: integer
      min: 0
      max: 255
      description: EEPROM data value (0-255)

- id: baud
  label: Set Baud Rate
  kind: action
  command: "BAUD {rate}\r"
  models: [RAV232]
  notes: "Power cycle after selection; external 9-15V DC at 50mA required for 9600 bps. UNRESOLVED: BAUD applicability to RAV232+ is not documented."
  params:
    - name: rate
      type: integer
      enum: [12, 96]
      description: Baud rate - 96 for 9600 bps, 12 for 1200 bps

# BAUD is documented in the RAV232 serial-configuration instructions, outside the command table.
- id: version_query
  label: Display Version Information
  kind: action
  command: "VER\r"
  params: []

- id: status_query
  label: Display Current House/Room/Channel Status
  kind: action
  command: "STATUS\r"
  params: []

- id: noecho
  label: Disable Character Echoing (RAV232+ only)
  kind: action
  command: "NOECHO\r"
  models: [RAV232+]
  notes: "Bi-directional model only; current echo mode is stored in non-volatile memory."
  params: []

- id: echo
  label: Enable Character Echoing (RAV232+ only)
  kind: action
  command: "ECHO\r"
  models: [RAV232+]
  notes: "Bi-directional model only; current echo mode is stored in non-volatile memory."
  params: []

Feedbacks

- id: ok
  label: Command Acknowledged
  type: string
  values:
    - ">OK"

- id: invalid_command
  label: Invalid Command Response
  type: string
  values:
    - ">Invalid Command!"

- id: status_response
  label: Status Output
  type: string
  pattern: "^HO:\\d{3} RO:\\d{3} CH:\\d{3}$"
  description: Returns current House, Room, and Channel as 3-digit zero-padded decimals

- id: version_response
  label: Version Info
  type: string
  description: Version string returned by VER command

# Bi-directional only - received events from Rako devices:
- id: button_event
  label: Button Event
  type: string
  pattern: "^<\\d{3}:\\d{2}:\\d{2}$"
  description: "<RRR:CC:IN - decimal room 0-255, channel 0-15, instruction number; line terminates with CR LF. Current HOUSE filters received events."
  # Instruction meanings depend on normal/program mode; see the complete Notes table.
  # UNRESOLVED: source event example labels instruction 01 as fade up, while its command table defines 1=LIGHT- and 2=LIGHT+. No unsupported resolution is claimed.

Variables

- id: echo_mode
  label: Echo Mode
  type: boolean
  writable: true
  description: Character echo toggle - NOECHO turns off, ECHO turns on. RAV232+ only.
  # Stored in non-volatile memory

Events

# RAV232+ only - unsolicited button press and system notifications
# Format: <RRR:CC:IN followed by CR LF
# House must be set via HOUSE command to filter output to current house only

Macros

# Multi-step sequences from source examples:
- id: set_scene_in_room
  label: Set Scene in Room
  steps:
    - 'ROOM <room_number>'
    - 'CHANNEL 0'
    - 'SCENE <scene_number>'
  description: Target all channels in a specific room to a specific scene

Safety

confirmation_required_for: []
interlocks:
  - desc: "RAV232 at 9600bps and RAV232+ must be powered by external 9-15V DC @ 50mA supply"
    # Source: "MUST be powered by an external supply of 9 to 15V DC @ 50mA"
  - desc: "RAV232+ hardware flow control - wait for '>' prompt before sending next command if CTS not connected"
  - desc: "Source warns CHANNEL or HOUSE 0 affects ALL dimmers when writing EEPROM; HOUSE setter itself documents only 1-255. ROOM 0 separately addresses all rooms in the current house."
    # Source: "if the channel or house number is set to zero as this will change the values on ALL the dimmers"

Notes

RAV232 is unidirectional (transmit only); RAV232+ is bidirectional and receives button-press events from Rako devices. The bidirectional unit only outputs messages for the current house address (set via HOUSE command). Commands are not case-sensitive and can be shortened (e.g., HOUSE:1 → HO:1). Delimiters: space, tab, or colon accepted. Character echoing is configurable on RAV232+ only (NOECHO/ECHO commands). EEPROM addresses 63-127 are profile data — should only be changed via RASOFT software.

Source: https://rakocontrols.com/media/1286/rs232-command-summary.pdf (four pages; ©2006 Rako). Transmit command text followed by CR (0x0D); the template notation \r denotes that byte. Arguments may use spaces, tabs or colons. Commands are case-insensitive and unambiguous abbreviations are accepted. The > prompt and echo are interface output, not bytes to prepend to requests. The source writes >OK and >Invalid Command! in its syntax description but examples show the prompt separately from OK; do not infer a fixed contiguous prompt/reply framing grammar. STATUS documents HO:nnn RO:nnn CH:nnn, without a required > prefix. VER has no documented exact response grammar.

All 16 documented command families are represented. ROOM and CHANNEL may omit their argument to select zero; the explicit-value templates above support that value without requiring the abbreviated form. BAUD is specified in the configuration instructions for RAV232, not as proof of RAV232+ rate switching.

Instruction meanings (blank cells mean no meaning specified for that mode; value 0 is accepted by the generic COMMAND range but has no table meaning):

InstructionNumber Instruction Program ModeInstruction
1 LIGHT -
2 LIGHT + LIGHT +
3 SCENE 1 LIGHT -
4 SCENE 2 STORE & IDENT
5 SCENE 3 CHANNEL +
6 SCENE 4 CHANNEL -
7 PROGRAM MODE
8 IDENT
9 IDENT
10 LOW BATTERY LOW BATTERY
11 EEPROM WRITE EEPROM WRITE
12 LEVEL SET LEVEL SET
13 STORE STORE
14 EXIT
15 STOP STOP

The fading instructions continue at the configured dimmer rate until STOP (15). The source's received-event example conflicts with the normal-mode LIGHT direction table; retain the numeric instruction and resolve behavior against further evidence before interpreting direction.

EEPROM write restrictions and values:

EEPROMAddress Action Notes
1 Scene 1 Preset Value -
2 Scene 2 Preset Value -
3 Scene 3 Preset Value -
4 Scene 4 Preset Value -
9 Power Up Mode(After Power Failure) 0 = Off1-4 = Scene5 = Last Scene6-255= Power Level
22 Ignore Program Mode >0 = Ignore
23 Ignore Group Commands >0 = Ignore
24 Ignore House Commands >0 = Ignore
26 Use Profile >0 = Use Profile
34 Scene Fade Rate 0 = Fast
36 Scene Fade Decay Rate 0 = No decay
40 Manual Fade Rate Max Sets The Maximum Rate
48 Manual Fade Rate Acceleration Sets The AccelarationTo Maximum
50 Manual Fade Rate Start Sets The Starting Fade Rate
63-127 Profile Data Determines the dimmers profile.These values should only bechanged usingRASOFT software

Select HOUSE, ROOM and CHANNEL before ADDRESS, then send DATA. Only the documented EEPROM locations may be written; 63-127 profile data is reserved for changes through RASOFT. The source's HOUSE 0 warning conflicts with the documented HOUSE 1-255 command range; it does not authorize an extra setter value. The 9-15V DC / 50mA requirement applies to RAV232 at 9600 and to RAV232+.

Provenance

source_domains:
  - rakocontrols.com
source_urls:
  - https://rakocontrols.com/media/1286/rs232-command-summary.pdf
retrieved_at: 2026-09-26T14:23:14.427Z
last_checked_at: 2026-09-26T14:23:14.427Z

Verification Summary

verdict: verified
checked_at: 2026-09-26T14:23:14.427Z
matched_actions: 16
action_count: 16
confidence: medium
summary: "Independently read the complete refined source and rendered all four pages of its official primary PDF. All16 action IDs/wire families and parameter ranges match:15 commands in the interface table plus BAUD in model-specific configuration. Complete COMMAND normal/program-mode and EEPROM tables are represented. RAV232 versus RAV232+ baud/flow/power/echo/event conditions agree with source. HOUSE0, instruction01 direction, prompt/reply framing and auth uncertainties are explicitly retained rather than resolved without evidence. No WRA232 source substitution. (4 unresolved item(s) noted in Known Gaps.)"

Known Gaps

- "BAUD applicability to RAV232+ is not documented.\""
- "source event example labels instruction 01 as fade up, while its command table defines 1=LIGHT- and 2=LIGHT+. No unsupported resolution is claimed."
- "firmware version — VER command exists but output format not captured"
- "complete firmware applicability and authentication are not specified."