Summary
The Panamax M7500-PRO is a sequenced power conditioner / outlet manager with an RS-232 control interface on a DB9 connector. This spec covers the ASCII command/response protocol used to switch outlet banks, configure triggers and delays, query power state, and enable unsolicited feedback.
Transport
protocols:
- serial
serial:
baud_rate: 9600
data_bits: 8
parity: none
stop_bits: 1
flow_control: none
null_modem: false # stated: "cable not required"
connector: DB9
connector_pinout:
pin2: RECEIVE DATA
pin3: TRANSMIT DATA
pin5: GROUND
auth:
type: none # inferred: no auth procedure in source
termination: "ASCII CR (13), LF (10), or NULL"
Traits
- powerable # inferred from power command examples
- routable # inferred from outlet bank switching examples
- queryable # inferred from query command examples
- levelable # inferred from !SET_BRIGHT (meter brightness) command
Actions
- id: button_on
label: Front Panel Button ON
kind: action
command: "!BUTTON_ON\r"
description: Changes the status of the front panel button to ON (equivalent to pressing the front panel button for 2 seconds).
response: "$BUTTON = ON\r"
params: []
- id: button_off
label: Front Panel Button OFF
kind: action
command: "!BUTTON_OFF\r"
description: Changes the status of the front panel button to OFF (equivalent to pressing the front panel button for 2 seconds).
response: "$BUTTON = OFF\r"
params: []
- id: all_off
label: All Outlets OFF
kind: action
command: "!ALL_OFF\r"
description: Turns off all outlets including always-on. Immediate, terminates any running sequence, overrides DC trigger input, sets front panel button OFF.
response: "$BUTTON = OFF\r"
params: []
- id: all_on
label: All Outlets ON
kind: action
command: "!ALL_ON\r"
description: Turns on all outlets. Immediate. Terminates any running sequence. Overrides DC trigger input, sets front panel button ON. Returns fault response on over/under-voltage.
response:
success: "$BUTTON = ON\r"
overvoltage: "$PWR = OVERVOLTAGE\r"
undervoltage: "$PWR = UNDERVOLTAGE\r"
params: []
- id: switch
label: Switch Outlet Bank
kind: action
command: "!SWITCH {bank} {state}\r"
description: Turns a specific outlet bank or the trigger output on or off (immediate, no delay).
response:
invalid: "$INVALID_PARAMETER\r"
confirmation: "see Feedbacks section 3.1"
overvoltage: "$PWR = OVERVOLTAGE\r"
undervoltage: "$PWR = UNDERVOLTAGE\r"
params:
- name: bank
type: string
enum: [1, 2, 3, 4, HC1, HC2, TRIGOUT]
- name: state
type: string
enum: [ON, OFF]
- id: set_bright
label: Set Meter Brightness
kind: action
command: "!SET_BRIGHT {x}\r"
description: Sets the voltmeter, ammeter and LED brightness to x%.
response:
valid: "$BRIGHTNESS = x\r"
invalid: "$INVALID_PARAMETER\r"
params:
- name: x
type: integer
min: 10
max: 100
- id: set_trigger
label: Set Trigger Source
kind: action
command: "!SET_TRIGGER {bank} {triggersource}\r"
description: Assigns the trigger(s) for an outlet bank or DC trigger output. Used in CUSTOM SETTINGS mode.
response:
valid: "$TRIGGER FOR {bank} = {triggersource}\r"
invalid: "$INVALID_PARAMETER\r"
params:
- name: bank
type: string
enum: [1, 2, 3, 4, HC1, HC2, TRIGOUT]
- name: triggersource
type: string
enum: [NONE, BUTTON, TRIGIN]
- id: set_delay
label: Set On/Off Delay
kind: action
command: "!SET_DELAY {bank} {ondelay} {offdelay}\r"
description: Assigns the turn-on and turn-off delays for an outlet bank or DC trigger output. Used in CUSTOM SETTINGS mode.
response:
valid: "$DELAY FOR {bank} = {ondelay} {offdelay}\r"
invalid: "$INVALID_PARAMETER\r"
params:
- name: bank
type: string
enum: [1, 2, 3, 4, HC1, HC2, TRIGOUT]
- name: ondelay
type: integer
min: 0
max: 240
unit: seconds
- name: offdelay
type: integer
min: 0
max: 240
unit: seconds
- id: set_feedback
label: Set Feedback Mode
kind: action
command: "!SET_FEEDBACK {mode}\r"
description: Sets feedback to ON (unsolicited) or OFF (polled). When ON, the unit sends a message whenever an input/output/power state changes.
response:
on: "$FEEDBACK = ON\r"
off: "$FEEDBACK = OFF\r"
invalid: "$INVALID_PARAMETER\r"
params:
- name: mode
type: string
enum: [ON, OFF]
- id: set_linefeed
label: Set Linefeed Mode
kind: action
command: "!SET_LINEFEED {mode}\r"
description: Controls linefeeds (ASCII 10 / 0x0A) appended to each response.
response:
on: "$LINEFEED = ON\r"
off: "$LINEFEED = OFF\r"
invalid: "$INVALID_PARAMETER\r"
params:
- name: mode
type: string
enum: [ON, OFF]
- id: reset_all
label: Reset All to Factory Defaults
kind: action
command: "!RESET_ALL\r"
description: Resets all custom configuration settings (triggers, delays, meter brightness, feedback mode, linefeed mode) to factory defaults.
response: "$FACTORY SETTINGS RESTORED\r"
factory_defaults:
TRIGGER FOR 1: BUTTON
TRIGGER FOR 2: BUTTON
TRIGGER FOR 3: BUTTON
TRIGGER FOR 4: BUTTON
TRIGGER FOR HC1: BUTTON
TRIGGER FOR HC2: BUTTON
TRIGGER FOR TRIGOUT: TRIGIN
DELAY FOR 1: "000,005"
DELAY FOR 2: "001,004"
DELAY FOR 3: "002,003"
DELAY FOR 4: "003,002"
DELAY FOR HC1: "004,001"
DELAY FOR HC2: "005,000"
DELAY FOR TRIGOUT: "005,000"
BRIGHTNESS: 100
FEEDBACK: ON
LINEFEED: ON
params: []
- id: query_id
label: Query Identity
kind: query
command: "?ID\r"
description: Request that the unit identify itself.
response:
- "$PANAMAX\r"
- "$MAX 74/7500-PRO\r"
- "$FIRMWARE {revision}\r"
params: []
- id: query_trigstat
label: Query Trigger Status
kind: query
command: "?TRIGSTAT\r"
description: Request the on/off status of the front panel button and input trigger.
response:
button_on: "$BUTTON = ON\r"
button_off: "$BUTTON = OFF\r"
trigin_on: "$TRIGIN = ON\r"
trigin_off: "$TRIGIN = OFF\r"
params: []
- id: query_outletstat
label: Query Outlet Status
kind: query
command: "?OUTLETSTAT\r"
description: Request the on/off status of the outlet banks and output trigger.
response_template:
BANK1: status
BANK2: status
BANK3: status
BANK4: status
HC1: status
HC2: status
TRIGOUT: status
status_values: [ON, OFF]
params: []
- id: query_powerstat
label: Query Power Status
kind: query
command: "?POWERSTAT\r"
description: Request the status of the input voltage.
response:
normal: "$PWR = NORMAL\r"
overvoltage: "$PWR = OVERVOLTAGE\r"
undervoltage: "$PWR = UNDERVOLTAGE\r"
recovery: "$PWR = RECOVERY\r"
params: []
- id: query_voltage
label: Query Line Voltage
kind: query
command: "?VOLTAGE\r"
description: Request the line voltage.
response:
in_range: "$VOLTAGE = {xxx}\r" # 140V > Vin > 90; leading zero for <100, e.g. 092
overvoltage: "$VOLTAGE = OVERVOLTAGE"
undervoltage: "$VOLTAGE = UNDERVOLTAGE"
params: []
- id: query_current
label: Query Input Current
kind: query
command: "?CURRENT\r"
description: Request the input current draw.
response: "$CURRENT = {xxx}\r" # decimal; leading zero for <10, e.g. 03.3
params: []
- id: query_help
label: Query Help
kind: query
command: "?HELP\r"
description: Request a list of all commands and queries.
response: "Listing of all commands and queries"
params: []
- id: query_list_config
label: Query Configuration
kind: query
command: "?LIST_CONFIG\r"
description: Request a list of all configurable parameters and current settings.
response_template:
- "$TRIGGER FOR 1 = {triggersource}\r"
- "$TRIGGER FOR 2 = {triggersource}\r"
- "$TRIGGER FOR 3 = {triggersource}\r"
- "$TRIGGER FOR 4 = {triggersource}\r"
- "$TRIGGER FOR HC1 = {triggersource}\r"
- "$TRIGGER FOR HC2 = {triggersource}\r"
- "$TRIGGER FOR TRIGOUT = {triggersource}\r"
- "$DELAY FOR 1 = {ondelay} {offdelay}\r"
- "$DELAY FOR 2 = {ondelay} {offdelay}\r"
- "$DELAY FOR 3 = {ondelay} {offdelay}\r"
- "$DELAY FOR 4 = {ondelay} {offdelay}\r"
- "$DELAY FOR HC1 = {ondelay} {offdelay}\r"
- "$DELAY FOR HC2 = {ondelay} {offdelay}\r"
- "$DELAY FOR TRIGOUT = {ondelay} {offdelay}\r"
- "$BRIGHTNESS = {x}\r"
- "$FEEDBACK = {x}\r"
- "$LINEFEED = {x}\r"
params: []
Feedbacks
- id: outlet_bank_state
type: object
description: Unsolicited feedback when an outlet bank or trigger output changes state (requires SET_FEEDBACK ON).
fields:
BANK1: enum [ON, OFF]
BANK2: enum [ON, OFF]
BANK3: enum [ON, OFF]
BANK4: enum [ON, OFF]
HC1: enum [ON, OFF]
HC2: enum [ON, OFF]
TRIGOUT: enum [ON, OFF]
example: "$BANK1 = ON\r"
- id: trigger_input_state
type: object
description: Unsolicited feedback when front panel button or input trigger changes state.
fields:
BUTTON: enum [ON, OFF]
TRIGIN: enum [ON, OFF]
example: "$BUTTON = OFF\r"
- id: power_overvoltage
type: enum
values: [OVERVOLTAGE]
description: Input voltage rose above the overvoltage threshold.
message: "$PWR = OVERVOLTAGE\r"
- id: power_undervoltage
type: enum
values: [UNDERVOLTAGE]
description: Input voltage fell below the undervoltage threshold.
message: "$PWR = UNDERVOLTAGE\r"
- id: power_recovery
type: enum
values: [RECOVERY]
description: Input voltage returned to safe operating range after an over/under-voltage condition.
message: "$PWR = RECOVERY\r"
- id: power_normal
type: enum
values: [NORMAL]
description: Recovery completed, normal operation resumed.
message: "$PWR = NORMAL\r"
Variables
- id: trigger_source
label: Trigger Source per Bank
type: string
enum: [NONE, BUTTON, TRIGIN]
description: Source that switches each outlet bank. NONE = always ON (RS-232 only). BUTTON = front panel button. TRIGIN = DC input trigger.
scope: per-bank (1, 2, 3, 4, HC1, HC2, TRIGOUT)
- id: on_delay
label: Turn-On Delay
type: integer
min: 0
max: 240
unit: seconds
description: Delay applied to outlet bank turn-on. Used in CUSTOM SETTINGS mode.
scope: per-bank (1, 2, 3, 4, HC1, HC2, TRIGOUT)
- id: off_delay
label: Turn-Off Delay
type: integer
min: 0
max: 240
unit: seconds
description: Delay applied to outlet bank turn-off. Used in CUSTOM SETTINGS mode.
scope: per-bank (1, 2, 3, 4, HC1, HC2, TRIGOUT)
- id: meter_brightness
label: Meter / LED Brightness
type: integer
min: 10
max: 100
unit: percent
description: Brightness of voltmeter, ammeter, and LEDs.
- id: feedback_mode
label: Feedback Mode
type: string
enum: [ON, OFF]
description: When ON, unit sends unsolicited state-change messages.
- id: linefeed_mode
label: Linefeed Mode
type: string
enum: [ON, OFF]
description: When ON, each response is terminated with a linefeed (LF / 0x0A) in addition to CR.
Events
- id: outlet_state_changed
description: An outlet bank or trigger output transitioned state.
payload: "$BANK{n} = {state}\r" # or $HC1, $HC2, $TRIGOUT
trigger: state change, requires feedback_mode=ON
- id: trigger_input_changed
description: Front panel button or DC input trigger changed state.
payload: "$BUTTON = {state}\r" or "$TRIGIN = {state}\r"
trigger: state change, requires feedback_mode=ON
- id: power_fault_overvoltage
description: Input voltage exceeded the overvoltage threshold.
payload: "$PWR = OVERVOLTAGE\r"
trigger: Vin > 140V
- id: power_fault_undervoltage
description: Input voltage dropped below the undervoltage threshold.
payload: "$PWR = UNDERVOLTAGE\r"
trigger: Vin < 90V
- id: power_fault_recovery
description: Input voltage re-entered safe range after a fault.
payload: "$PWR = RECOVERY\r"
trigger: 90V <= Vin <= 140V after fault
- id: power_fault_normal
description: Recovery completed, normal operation resumed.
payload: "$PWR = NORMAL\r"
trigger: post-recovery transition
Macros
# No multi-step sequences explicitly described in source.
# All commands in the source are atomic. UNRESOLVED: not applicable.
Safety
confirmation_required_for: []
interlocks:
- "!ALL_OFF and !ALL_ON terminate any running turn-on/turn-off sequence and override the DC trigger input."
- "Over/under-voltage faults abort !ALL_ON and return $PWR = OVERVOLTAGE / UNDERVOLTAGE."
# UNRESOLVED: no explicit safety warnings, no interlock procedures, no power-on sequencing requirements stated in source beyond immediate switch behavior.
Notes
- Source describes only RS-232 on DB9 (no TCP/IP, REST, or other network protocol documented). The "Known protocol" hint (TCP/IP) in the intake did not match the source — spec reflects source.
- All commands and responses are ASCII terminated by CR (0x0D), LF (0x0A), or NULL. SET_LINEFEED controls whether LF is appended to responses.
- DB9 wiring: pin 2 = RX, pin 3 = TX, pin 5 = GND. Null-modem cable not required (suggests the M7500-PRO is already wired as a DTE or uses straight-through to host DTE; see source page 2 for diagram).
- ID response advertises the model string "MAX 74/7500-PRO" — preserved as-is in compatible_with and query_id.
- Factory defaults stored in non-volatile EEPROM are restored by !RESET_ALL.
Provenance
source_domains:
- panamax.com
source_urls:
- https://panamax.com/wp-content/uploads/m7500pro_manual.pdf
retrieved_at: 2026-06-03T11:10:08.022Z
last_checked_at: 2026-06-04T06:28:51.084Z
Verification Summary
verdict: verified
checked_at: 2026-06-04T06:28:51.084Z
matched_actions: 19
action_count: 19
confidence: medium
summary: "All 19 spec commands matched verbatim in source with correct parameters and transport settings verified. (4 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "known protocol was given as TCP/IP, but the source document describes only RS-232. No TCP/IP control documented."
- "not applicable."
- "no explicit safety warnings, no interlock procedures, no power-on sequencing requirements stated in source beyond immediate switch behavior."
- "firmware version compatibility not stated in source. UNRESOLVED: DC trigger voltage/current ranges (3-24V, 4.6mA@3V, 58mA@24V in, <12V/<400mA out) are documented but are hardware electrical specs, not control-protocol fields — included in Notes context only."