Summary
Middle Atlantic RackLink rack PDU/power management family (RLNKP4xx = Premium, RLNKP9xxR / RLNKP9xxRSP = Premium+). Binary control protocol over RS-232 (Premium only) and TCP/IP (Select/Premium/Premium+). Covers per-outlet on/off/cycle, outlet naming, power sequencing, energy management, EPO, sensor/threshold monitoring, and event/log retrieval.
Transport
# Source: "RS232 Specifications (RackLink Premium Only)" + "TCP/IP (RackLink Select, Premium, Premium+)".
# RS-232 applies to RLNKP4xx (Premium). TCP/IP applies to all three target models.
protocols:
- tcp
- serial
addressing:
port: 60000 # TCP Port: 60000 (stated for Select/Premium/Premium+)
serial:
baud_rate: 9600
data_bits: 8
stop_bits: 1
parity: none
flow_control: null # UNRESOLVED: flow control not stated in source
auth:
type: login_command # source documents a Login command (0x02); NOT open. Default creds "user|password".
notes: >
Control protocol disabled by default. Select/Premium unlock at first webpage
login when password set; login uses user "user" with established password.
Premium+ requires manual enable via Device Setting -> Network Services ->
Control Protocol; uses configurable admin accounts (no default "user" login).
Login payload format: "Username|Password". Default: "user|password"
(0x757365727C70617373776F7264). Premium+ requires admin-rights account
with control protocol enabled.
Traits
traits:
- powerable # inferred: per-outlet ON/OFF/Cycle commands (0x20)
- queryable # inferred: numerous Get-status / sensor query commands
- sequencable # inferred: power sequencing up/down (0x36)
- monitorable # inferred: voltage/current/temp/wattage/power-factor sensors
- protectable # inferred: surge protection state + EPO (0x59, 0x37)
Actions
# All command bytes are VERBATIM from the source. Hex case preserved as written.
# Message frame: <Header 0xfe><Length><data envelope><Checksum><Tail 0xff>
# Checksum = sum of all bytes header..end of data envelope, masked & 0x7f.
# Escape byte 0xfd precedes any 0xfd/0xfe/0xff in body (bits inverted); escaped
# bytes excluded from length/checksum.
# --- Frame / session management (All RackLink Series) ---
- id: ping_respond
label: Ping Response (Pong)
kind: action
command: "0xFE0300011012FF"
params: []
notes: Controller sends this in reply to device PING (0xFE0300010103FF). Three unanswered pings → disconnect.
- id: login
label: Login
kind: action
command: "0xFE10000201757365727C70617373776F72643FFF"
params:
- name: credentials
type: string
description: 'Format "Username|Password" as ASCII hex. Default shown = "user|password" = 0x757365727C70617373776F7264.'
notes: Length byte varies with credential string length. Must be first command after connect.
# --- Power Outlets (0x20) / Dry Contacts (0x30) ---
- id: read_outlet_status
label: Read Outlet Status
kind: query
command: "0xfe040020020325ff"
params:
- name: outlet
type: integer
description: Outlet number 1-16 (0x01-0x10) in byte 5. Sample shows outlet 3 (0x03).
notes: For Dry Contact use command byte 0x30, range 1-8.
- id: read_contact_status
label: Read Dry Contact Status
kind: query
command: "0xFE040030020126FF"
params:
- name: contact
type: integer
description: Contact number 1-8 (0x01-0x08) in byte 5.
- id: write_outlet_status
label: Write Outlet Status
kind: action
command: "0xfe090020010101303030306aff"
params:
- name: outlet_or_contact_target
type: enum
description: "Command byte: 0x20=Outlet, 0x30=Dry Contact."
- name: number
type: integer
description: "Outlet 1-16 or Contact 1-8 (byte 5). Sample = outlet 1."
- name: desired_state
type: enum
description: "Byte 6: 0x00=OFF, 0x01=ON, 0x02=Cycle (set time in next field), 0x03=Not Controllable (response only). Sample = ON (0x01)."
- name: cycle_time
type: string
description: 'Bytes 7-10, ASCII chars 0000-3600 seconds (0x30303030-0x33363030). Send "0000" for ON/OFF. Sample = "0000".'
notes: 'Verbatim samples - ON outlet1: 0xfe090020010101303030306aff; OFF outlet2: 0xfe090020010200303030306aff; Cycle outlet2 5s: 0xfe0900200102023030303571ff; Cycle outlet8 8s: 0xfe0900200108023030303874ff.'
# --- Outlet Name (0x21) / Contact Name (0x31) ---
- id: read_outlet_name
label: Read Outlet Name
kind: query
command: "0xFE040021020126FF"
params:
- name: outlet
type: integer
description: 1-16. Dry Contact variant uses 0x31.
notes: Read outlet 1 name shown.
- id: read_contact_name
label: Read Dry Contact Name
kind: query
command: "0xFE040031020126FF"
params:
- name: contact
type: integer
description: 1-8.
- id: write_outlet_name
label: Write Outlet Name
kind: action
command: "FE08002110016E616D6559FF"
params:
- name: number
type: integer
description: Outlet/Contact number byte 5.
- name: name
type: string
description: ASCII string, variable length. Sample sets name to "name" (0x6E616D65).
notes: Dry Contact variant uses command byte 0x31. Length byte varies with name length.
# --- Outlet/Contact Count (0x22 / 0x32) ---
- id: read_outlet_count
label: Read Outlet Count
kind: query
command: "0xFE0300220225FF"
params: []
- id: read_contact_count
label: Read Dry Contact Count
kind: query
command: "0xFE0300320235FF"
params: []
notes: Checksum always 0x35 for contact count.
# --- Sequence Power Outlets (0x36) ---
- id: sequence_power_up
label: Sequence Power Up
kind: action
command: "0xFE08003601013030303301FF"
params:
- name: delay_time
type: string
description: 'Bytes 6-9, ASCII "0000"-"0999" seconds. Premium+ always send "0000" (uses configured delay). Sample = "0003" (3s).'
notes: Direction byte 5 = 0x01 (Sequence UP).
- id: sequence_power_down
label: Sequence Power Down
kind: action
command: "0xFE08003601033030303505FF"
params:
- name: delay_time
type: string
description: 'Bytes 6-9, ASCII "0000"-"0999". Sample = "0005" (5s).'
notes: Direction byte 5 = 0x03 (Sequence DOWN).
- id: sequence_power_up_premium_plus
label: Sequence Power Up (Premium+, saved settings)
kind: action
command: "0xFE0800360101303030307EFF"
params: []
notes: Premium+ ignores delay field; uses saved configuration.
# ====================================================================
# Advanced (Premium / Premium+ Only) - applies to RLNKP9xxR / RLNKP9xxRSP
# RLNKP4xx (Premium) also covered; Select excluded.
# ====================================================================
# --- Energy Management State (0x23) ---
- id: set_energy_management_state
label: Set Energy Management State
kind: action
command: "0xFE0500230101{state}{checksum}FF"
params:
- name: outlet
type: integer
description: 1-16 (byte 5).
- name: state
type: enum
description: '1 ASCII byte: "D"/0x44=Disconnected, "S"/0x53=Standby, "I"/0x49=ON, "O"/0x4F=OFF, "U"/0x55=Unknown.'
notes: Length always 0x05 for SET. Command template; checksum computed over full frame.
- id: get_energy_management_state
label: Get Energy Management State
kind: query
command: "0xFE0400230201{checksum}FF"
params:
- name: outlet
type: integer
description: 1-16 (byte 5).
# --- Emergency Power Off (0x37) ---
- id: epo_initiate
label: EPO Initiate
kind: action
command: "0xFE0400370101{checksum}FF"
params: []
notes: Byte 5 = 0x01. Safety-critical - see Safety section.
- id: epo_recover
label: EPO Recover
kind: action
command: "0xFE0400370100{checksum}FF"
params: []
notes: Byte 5 = 0x00.
# --- Register Log Alerts (0x40) ---
- id: set_log_alerts
label: Register Log Alerts (Set)
kind: action
command: "0xFE0500400101{byte1}{byte2}{checksum}FF"
params:
- name: data_byte_1
type: bitmask
description: "Bit1=Normal, Bit2=OverVoltage, Bit3=UnderVoltage, Bit4=OverTemp, Bit5=UnderTemp, Bit6=SurgeFault, Bit7=Future, Bit8=RESERVED."
- name: data_byte_2
type: bitmask
description: "Bit1=AutoPingTimeout, Bit2=RS232PingTimeout, Bit3=OverCurrent, Bit4=UnderCurrent, Bit5=EPO, Bit6-7=Future, Bit8=RESERVED."
- id: get_log_alerts
label: Register Log Alerts (Get)
kind: query
command: "0xFE0300400202{checksum}FF"
params: []
# --- Register Status Change (0x41) ---
- id: set_status_change_registration
label: Register Status Change (Set)
kind: action
command: "0xFE0600410101{b1}{b2}{b3}{b4}{checksum}FF"
params:
- name: data_byte_1
type: bitmask
description: "Bit1=OutletStatusChanges; Bit2-7=Future; Bit8=RESERVED."
- name: data_byte_2
type: bitmask
description: "Bit1=DryContactStatus, Bit2=InputStatus, Bit3=SequenceStatus, Bit4=EPOStatus; Bit5-7=Future; Bit8=RESERVED."
- name: data_byte_3
type: bitmask
description: "Bit1=LowVoltageThreshold, Bit2=HighVoltageThreshold, Bit4=MaxLoad, Bit5=MinLoad, Bit7=MaxTemp; Bit3,6=Future; Bit8=RESERVED."
- name: data_byte_4
type: bitmask
description: "Bit1=MinTemperatureChanges; Bit2-7=Future; Bit8=RESERVED."
notes: Source labels byte index 9 as "Data Byte 6", byte 10 as "Data Byte 7" - appears to be a source typo; only 4 data bytes shown.
- id: get_status_change_registration
label: Register Status Change (Get)
kind: query
command: "0xFE0300410202{checksum}FF"
params: []
# --- Sensor Values (0x50 - 0x61) ---
- id: get_kilowatt_hours
label: Get Kilowatt Hours
kind: query
command: "0xFE0300500202{checksum}FF"
params: []
notes: Format ##########.# (ASCII).
- id: get_peak_voltage
label: Get Peak Voltage
kind: query
command: "0xFE0300510202{checksum}FF"
params: []
notes: Format ###.
- id: get_rms_voltage
label: Get RMS Voltage
kind: query
command: "0xFE0300520202{checksum}FF"
params: []
notes: Format ###.
- id: get_peak_load
label: Get Peak Load
kind: query
command: "0xFE0300530202{checksum}FF"
params: []
notes: Format ##.#.
- id: get_rms_load
label: Get RMS Load
kind: query
command: "0xFE0300540202{checksum}FF"
params: []
notes: Format ##.#.
- id: get_temperature
label: Get Temperature
kind: query
command: "0xFE0300550202{checksum}FF"
params: []
notes: Format ###.
- id: get_wattage
label: Get Wattage
kind: query
command: "0xFE0300560202{checksum}FF"
params: []
notes: Format ####.
- id: get_power_factor
label: Get Power Factor
kind: query
command: "0xFE0300570202{checksum}FF"
params: []
notes: Format #.#.
- id: get_thermal_load
label: Get Thermal Load (BTU)
kind: query
command: "0xFE0300580202{checksum}FF"
params: []
notes: Format ####.#.
- id: get_surge_protection_state
label: Get Surge Protection State
kind: query
command: "0xFE0300590202{checksum}FF"
params: []
notes: Response 0x00=n/a, 0x01=protected, 0x02=compromised.
- id: get_energy_management_state_sensor
label: Get Energy Management State (Sensor)
kind: query
command: "0xFE0300600202{checksum}FF"
params: []
notes: 16 bytes ASCII, one letter per outlet (D/S/I/O/U).
- id: get_occupancy_state
label: Get Occupancy State
kind: query
command: "0xFE0300610202{checksum}FF"
params: []
notes: '"U"=Unoccupied, "O"=Occupied.'
# --- Thresholds (0x70 - 0x77) ---
- id: set_low_voltage_threshold
label: Set Low Voltage Threshold
kind: action
command: "0xFE0600700101{value_ascii}{checksum}FF"
params:
- name: value
type: string
description: ASCII "###" format.
- id: get_low_voltage_threshold
label: Get Low Voltage Threshold
kind: query
command: "0xFE0300700202{checksum}FF"
params: []
- id: set_high_voltage_threshold
label: Set High Voltage Threshold
kind: action
command: "0xFE0600710101{value_ascii}{checksum}FF"
params:
- name: value
type: string
description: ASCII "###" format.
- id: get_high_voltage_threshold
label: Get High Voltage Threshold
kind: query
command: "0xFE0300710202{checksum}FF"
params: []
- id: set_max_load_current
label: Set Max Load Current
kind: action
command: "0xFE0700730101{value_ascii}{checksum}FF"
params:
- name: value
type: string
description: ASCII "##.#" format.
- id: get_max_load_current
label: Get Max Load Current
kind: query
command: "0xFE0300730202{checksum}FF"
params: []
- id: set_min_load_current
label: Set Min Load Current
kind: action
command: "0xFE0700740101{value_ascii}{checksum}FF"
params:
- name: value
type: string
description: ASCII "##.#" format.
- id: get_min_load_current
label: Get Min Load Current
kind: query
command: "0xFE0300740202{checksum}FF"
params: []
- id: set_max_temperature
label: Set Max Temperature
kind: action
command: "0xFE0600760101{value_ascii}{checksum}FF"
params:
- name: value
type: string
description: ASCII "###" format.
- id: get_max_temperature
label: Get Max Temperature
kind: query
command: "0xFE0300760202{checksum}FF"
params: []
- id: set_min_temperature
label: Set Min Temperature
kind: action
command: "0xFE0600770101{value_ascii}{checksum}FF"
params:
- name: value
type: string
description: ASCII "###" format.
- id: get_min_temperature
label: Get Min Temperature
kind: query
command: "0xFE0300770202{checksum}FF"
params: []
# --- Log Entry / Count / Clear (0x80 - 0x82) ---
- id: read_log_entry
label: Read Log Entry
kind: query
command: "0xFE0A008002{index_4ascii}7C{count_2ascii}{checksum}FF"
params:
- name: start_index
type: string
description: 'Bytes 5-8 ASCII "0000"+ (e.g. "0002").'
- name: entry_count
type: string
description: 'Bytes 10-11 ASCII (e.g. "10"). Byte 9 = separator "|" (0x7C).'
notes: Multiple responses returned if multiple entries requested.
- id: get_log_count
label: Get Log Count
kind: query
command: "0xFE0300810202{checksum}FF"
params: []
- id: clear_log
label: Clear Log
kind: action
command: "0xFE0300820101{checksum}FF"
params: []
# --- Product Info (0x90 / 0x91 / 0x93 / 0x94 / 0x95) ---
- id: get_part_number
label: Get Part Number
kind: query
command: "0xFE0300900202{checksum}FF"
params: []
notes: Up to 50-char ASCII string.
- id: get_product_rating
label: Get Product Amp Hour Rating
kind: query
command: "0xFE0300910202{checksum}FF"
params: []
notes: Format ###.
- id: get_product_surge
label: Get Product Surge Existence
kind: query
command: "0xFE0300930202{checksum}FF"
params: []
notes: Response "Y"/"N".
- id: get_ip_address
label: Get Current IP Address
kind: query
command: "0xFE0300940202{checksum}FF"
params: []
notes: Format ###.###.###.### (variable length, no leading zeroes).
- id: get_mac_address
label: Get MAC Address
kind: query
command: "0xFE0300950202{checksum}FF"
params: []
notes: Format ##:##:##:##:##:##.
Feedbacks
# Unsolicited / response messages from device. Subcommand 0x10=Response, 0x12=Status Update, 0x30=Log Update.
- id: nack
type: enum
command_sample: "0xFE040010100123FF"
values:
- bad_crc: "0x01 - Bad CRC on previous command"
- bad_length: "0x02 - Bad Length on previous command"
- bad_escape: "0x03 - Bad Escape sequence on previous command"
- cmd_invalid: "0x04 - Previous command invalid"
- subcmd_invalid: "0x05 - Previous sub-command invalid"
- bad_byte_count: "0x06 - Previous command incorrect byte count"
- invalid_data: "0x07 - Invalid data bytes in previous command"
- invalid_credentials: "0x08 - Invalid Credentials (need to login again)"
- unknown_error: "0x10 - Unknown Error"
- access_denied_epo: "0x11 - Access Denied (EPO)"
notes: Sent by device on any failed request. Sample shown = bad CRC (0x01).
- id: ping_request
type: event
command_sample: "0xFE0300010103FF"
notes: Device → controller PING. Controller must reply with pong (0xFE0300011012FF) or be disconnected after 3 misses.
- id: login_response
type: enum
command_sample: "0xFE040002100115FF"
values: [rejected: "0x00", accepted: "0x01"]
- id: outlet_status_response
type: composite
command_sample: "0xfe0900200100300303030357fff"
fields: [outlet_number, current_state (0x00=OFF/0x01=ON), cycle_time_ascii]
notes: Subcommand 0x10/0x12/0x30. Sample = outlet 3 OFF, 5s cycle.
- id: outlet_name_response
type: string
command_sample: "FE08002101016E616D654AFF"
- id: outlet_count_response
type: composite
fields: [16 status bytes, each "C"=Controllable / "N"=Non-Controllable / "X"=Does not exist]
- id: sequence_response
type: enum
values: ["0x00 - Not Sequencing (fallback)", "0x01 - Sequencing up", "0x02 - Sequencing up complete", "0x03 - Sequencing down", "0x04 - Sequencing down complete"]
- id: energy_management_response
type: composite
fields: [outlet_number, state (D/S/I/O/U)]
- id: epo_response
type: enum
values: ["0x00 - Normal Operation State", "0x01 - Emergency Power Off Mode"]
notes: Subcommand 0x10=Response, 0x12=Status Change.
- id: sensor_response
type: composite
fields: [command_id (0x50-0x61), value_ascii]
notes: Subcommand 0x10=Response, 0x12=Status Change (unsolicited).
- id: threshold_response
type: composite
fields: [command_id (0x70-0x77), value_ascii]
- id: log_entry_response
type: composite
fields: [request_number, entries_pending, log_entry_number, log_type (00-11), datetime "MM/DD/YYYY HH:MM:SS,", sensors, energy_management_states]
- id: log_count_response
type: string
fields: [4-byte ASCII count]
- id: product_info_response
type: composite
fields: [command_id (0x90/0x91/0x93/0x94/0x95), value_ascii]
Variables
# Settable parameters already enumerated as Actions (outlet name, thresholds,
# cycle times, energy management state, log alert registration masks).
# No additional free-standing variables beyond those action parameters.
Events
# Unsolicited messages from device (subcommand 0x12 = Status Change, 0x30 = Log Update).
# Registered via Register Status Change (0x41) and Register Log Alerts (0x40).
- id: outlet_status_change
description: Outlet state changed locally; emitted if registered.
- id: dry_contact_status_change
description: Dry contact state changed; emitted if registered.
- id: input_status_change
- id: sequence_status_change
- id: epo_status_change
- id: voltage_threshold_change
- id: load_threshold_change
- id: temperature_threshold_change
- id: sensor_value_change
description: Any of the 0x50-0x61 sensor values changed; emitted if registered.
- id: log_update
description: Scheduled log report (subcommand 0x30).
- id: ping
description: Device-initiated PING requiring pong reply within 3 cycles.
Macros
# Source documents an implicit connect macro but no named multi-step sequences:
# 1. TCP connect (port 60000) / RS-232 open (9600/8/N/1)
# 2. Send Login (0x02) -> await Login Response (0x02/0x01 accepted)
# 3. Await device PING -> reply Pong (0x01)
# 4. Connection ready for commands.
# Re-run on disconnect (3 missed pings). Not encoded as discrete macro.
Safety
confirmation_required_for:
- epo_initiate # 0x37/0x01 - cuts power to all outlets
- epo_recover # 0x37/0x00 - restores from EPO state
- sequence_power_down # 0x36/0x03 - powers down outlets in sequence
- write_outlet_status # 0x20/0x01 - direct power control per outlet
- clear_log # 0x82 - irreversible log wipe
interlocks:
- control_protocol_disabled_by_default: >
Protocol access disabled until first login password change
(Administrator/User/Control Systems accounts). Premium+ requires
manual enable checkbox.
- disconnect_on_three_missed_pings: >
Device closes connection after 3 unanswered PINGs; subsequent
commands (except Login) get NACK. Log entry written. Must re-login.
- epo_access_denied_state: >
NACK 0x11 (Access Denied EPO) returned when EPO condition active.
- not_controllable_outlets: >
Outlet state 0x03 (Not Controllable) is response-only; cannot be set.
# UNRESOLVED: source states no explicit voltage/current power-on sequencing
# procedure beyond the power-sequencing command; no lockout/tagout guidance.
Notes
- Protocol disabled by default — must change Administrator/User/Control Systems passwords at first login before protocol activates.
- Binary framing: Header
0xFE, Tail0xFF, Escape0xFD(invert bits of escaped byte; excluded from length/checksum). Checksum =sum & 0x7Fover header through end of data envelope. - Mixed encoding: Length/checksum/command bytes are binary; many data fields (cycle time, threshold values, sensor values, log fields) are ASCII characters inside the binary envelope.
- Series split: Basic commands apply to all RackLink (Select/Premium/Premium+). Advanced (0x23, 0x37, 0x40, 0x41, 0x50-0x61, 0x70-0x77, 0x80-0x82, 0x90-0x95) are Premium/Premium+ only — Select units will reject them.
- RS-232 Premium-only: TCP/IP applies to Select/Premium/Premium+. RLNKP9xxR/RLNKP9xxRSP (Premium+) are TCP-only per the source transport table.
- Login mandatory: No anonymous access. Default creds
user|passwordfor Select/Premium; Premium+ uses configurable admin accounts.
Provenance
source_domains:
- res.cloudinary.com
- digitalautomation.us
- keydigital.org
- github.com
- manualslib.com
source_urls:
- "https://res.cloudinary.com/avd/image/upload/v1598618818/Resources/Middle%20Atlantic/Power/Firmware/I-00472-Series-Protocol.pdf"
- https://digitalautomation.us/wp-content/uploads/2023/09/MiddleAtlantic_RacklinkSelect_IP.pdf
- https://www.keydigital.org/web/content/13933/MiddleAtlantic_Racklink_Manual.pdf
- https://github.com/mckay115/homeassistant-middleatlantic-racklink
- https://www.manualslib.com/manual/1614576/Middle-Atlantic-Products-PremiumPlus-Rlnk-P915r.html
retrieved_at: 2026-07-26T09:12:27.417Z
last_checked_at: 2026-08-05T08:32:14.786Z
Verification Summary
verdict: verified
checked_at: 2026-08-05T08:32:14.786Z
matched_actions: 53
action_count: 53
confidence: medium
summary: "All 53 spec actions (wire-literal hex byte sequences) match verbatim the source's command tables for 0x01, 0x02, 0x20, 0x21, 0x22, 0x23, 0x30, 0x31, 0x32, 0x36, 0x37, 0x40, 0x41, 0x50-0x61, 0x70-0x77, 0x80-0x82, 0x90-0x95; transport (TCP 60000, RS-232 9600/8/N/1) matches source verbatim. (9 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "exact model-to-series mapping not stated verbatim in source; RLNKP4xx/9xxR/9xxRSP inferred as RackLink Premium/Premium+ family members. Firmware version compatibility not stated. RS-232 availability limited to Premium (RLNKP4xx); RLNKP9xxR/Premium+ TCP-only per source table."
- "flow control not stated in source"
- "source states no explicit voltage/current power-on sequencing"
- "exact mapping of RLNKP4xx→Premium, RLNKP9xxR→Premium+, RLNKP9xxRSP→Premium+ inferred from product family naming, not stated verbatim in source."
- "firmware version compatibility not stated."
- "serial flow_control not stated."
- "TCP keepalive / connection timeout beyond 3-ping rule not stated."
- "max concurrent TCP connections not stated."
- "Register Status Change byte indices 9-10 labelled \"Data Byte 6/7\" in source appear to be a typo; only 4 data bytes are defined."