Summary
Leviton IF501 (Vizia RF + VRC0P) RS-232 serial interface module for Z-Wave network control. Provides ASCII command protocol over serial for controlling lighting (on/off/dim/bright), scenes, groups, thermostats, door locks, and generic Z-Wave devices. Message format uses > prefix with uppercase ASCII commands, max 80 characters per line.
Transport
protocols:
- serial
serial:
baud_rate: 9600
data_bits: 8
parity: none
stop_bits: 1
flow_control: none
auth:
type: none # inferred: no auth procedure in source
Traits
- powerable # ON/OFF commands
- levelable # L (level 0-100%), DI, BR commands
- queryable # ? (request), UP (update) commands
Actions
- id: node_associate
label: Associate Nodes
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers (e.g. "2,3,5")
notes: ">N2,3,5 associates nodes. >N with no args clears association."
- id: power_on
label: Power On
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers, or empty for broadcast
notes: "Example: >N2ON or >N,ON (broadcast)"
- id: power_off
label: Power Off
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers, or empty for broadcast
notes: "Example: >N2,5,10OFF"
- id: set_level
label: Set Level
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers
- name: level
type: integer
description: Light level 0-100 percent
- id: group_recall
label: Group Recall
kind: action
params:
- name: group
type: integer
description: Group number (stored via GS command)
notes: "Follow with a control command on next line (e.g. >ON, >L50)"
- id: scene_activate
label: Activate Scene
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers
- name: scene
type: integer
description: Scene number (2-255)
- name: fade_rate
type: integer
required: false
description: Fade rate (1-255), optional
- id: dim
label: Dim
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers
notes: "Dims toward 0%. Stop with ST command."
- id: bright
label: Brighten
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers
notes: "Brightens toward 99%. Stop with ST command."
- id: stop
label: Stop Dim/Bright
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers
notes: "Stops active DI/BR operation. Needs 1-2ms between DI and BR commands."
- id: send_zwave
label: Send Z-Wave Command
kind: action
params:
- name: nodes
type: string
description: Target node number(s)
- name: command_class
type: integer
description: Z-Wave command class number
- name: command
type: integer
description: Z-Wave command number
- name: params
type: string
required: false
description: Additional command parameters (comma-separated)
notes: "Raw Z-Wave message. Example: >N5SE68,1,1"
- id: secure_send
label: Secure Send Z-Wave Command
kind: action
params:
- name: nodes
type: string
description: Target node number(s)
- name: command_class
type: integer
description: Z-Wave command class number
- name: command
type: integer
description: Z-Wave command number
- name: params
type: string
required: false
description: Additional command parameters (comma-separated)
notes: "Encrypted Z-Wave message for security devices. Requires VRC0P with +3 label."
- id: group_store
label: Store Group
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers
- name: group
type: integer
description: Group number to store
- id: program_scene
label: Program Scene
kind: action
params:
- name: nodes
type: string
description: Comma-separated node numbers
- name: scene
type: integer
description: Scene number (2-255)
- name: fade_rate
type: integer
required: false
description: Fade rate (1-255)
- id: set_node_name
label: Set Node Name
kind: action
params:
- name: node
type: integer
description: Node number
- name: charset
type: integer
description: "0=ASCII, 1=extended ASCII (recommended), 2=Unicode UTF-8"
- name: name
type: string
description: "Name up to 16 characters"
- id: set_node_location
label: Set Node Location
kind: action
params:
- name: node
type: integer
description: Node number
- name: charset
type: integer
description: "0=ASCII, 1=extended ASCII (recommended), 2=Unicode UTF-8"
- name: location
type: string
description: "Location up to 16 characters"
- id: append
label: Append Command
kind: action
params:
- name: continuation
type: string
description: Continuation of command exceeding 80 chars
notes: "Extends previous command line. Example: >AP,25,26,ON"
- id: set_speed
label: Set Communication Speed
kind: action
params:
- name: speed
type: integer
description: "0=9600, 1=19200, 2=38400, 3=57600, 4=115200"
notes: "Requires VRC0P with +3 label. Reverts to 9600 on power cycle."
- id: factory_default
label: Factory Default
kind: action
params: []
notes: "Must hold LED button while sending DE command."
- id: include_exclude
label: Include/Exclude
kind: action
params: []
notes: "Puts RS232 module into network include/exclude mode."
- id: abort
label: Abort
kind: action
params: []
notes: "Cancels any previous transmission."
- id: set_routes
label: Assign/Delete Routes
kind: action
params:
- name: source_node
type: integer
description: Routing slave node number
- name: target_node
type: integer
description: "Target node. 0 to delete all routes for source."
Feedbacks
- id: error_code
type: enum
values: [E000, E001, E002, E003, E004, E005, E006, E007, E008, E009, E010]
description: >
E000=no error, E001=wrong start symbol, E002=input buffer overflow,
E003=cannot start RF (buffers full), E004=previous RF not finished,
E005=unrecognized command, E006=RS232 buffer collision,
E007=send message missing data fields, E008=cannot stop SUC mode,
E009=EEPROM busy, E010=no devices found
- id: transmission_result
type: enum
values: [X000, X002]
description: "X000=success, X002=transmission error"
- id: node_report
type: string
description: >
Unsolicited report from nodes. Format: <Nxxx:ccc,mmm,...>
xxx=node ID, ccc=command class, mmm=command/data bytes.
Security responses use lowercase 'n' prefix.
- id: find_result
type: string
description: "Node ID found. Format: <Fxxx where xxx is node ID."
- id: node_level_report
type: string
description: >
Level report from update/request. Format: <Nxxx:044,003,sss,lll,fff>
sss=scene number, lll=light level, fff=fade rate
Variables
# UNRESOLVED: no distinct settable variables beyond action parameters identified in source
Events
- id: unsolicited_node_report
description: >
Device forwards incoming Z-Wave messages to serial output as
<Nxxx:...> or <nxxx:...> (security). Occurs when nodes send
unsolicited reports to the serial interface.
- id: network_change
description: >
Interface replies after adding/removing itself to/from a Z-Wave network.
Macros
- id: dimmer_off_sequence
steps:
- ">N2OFF"
- ">N2UP"
notes: "Turn dimmer OFF with update. Source appendix D."
- id: set_level_with_update
steps:
- ">N2L50UP"
notes: "Set level and request update in single command. Source appendix D."
Safety
confirmation_required_for: []
interlocks: []
# UNRESOLVED: no explicit safety warnings or interlock procedures in source.
# Factory default (DE) requires physical button hold - noted in action params.
Notes
- All commands must use uppercase letters and start with
>prefix. - Input string limited to 80 characters; use AP (append) to extend.
- Communication speed reverts to 9600 baud after power cycle.
- Secure Send (SS) requires VRC0P hardware revision with +3 on back label.
- Update (UP) command recommended over Request (?) for status queries; wait a few seconds between control command and update command.
- Z-Wave routing slaves support up to 5 return routes via RO command.
Provenance
source_domains:
- leviton.com
- applicationmarket.crestron.com
source_urls:
- https://leviton.com/content/dam/leviton/residential/product_documents/application_note/VRC0P_ASCII_Programming_Application_Note.pdf
- https://applicationmarket.crestron.com/content/Help/Leviton/dimensions_3000.pdf
retrieved_at: 2026-05-14T23:54:54.918Z
last_checked_at: 2026-06-02T22:08:46.986Z
Verification Summary
verdict: verified
checked_at: 2026-06-02T22:08:46.986Z
matched_actions: 21
action_count: 21
confidence: medium
summary: "All 21 spec actions traced to source (dip-safe re-verify). (8 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "device model IF501 inferred from entity_id; source references \"Vizia RF + VRC0P\" — exact model correspondence not confirmed"
- "no distinct settable variables beyond action parameters identified in source"
- "no explicit safety warnings or interlock procedures in source."
- "exact model number IF501 vs VRC0P correspondence not confirmed in source"
- "maximum number of nodes/groups supported not stated"
- "firmware version compatibility not stated"
- "command timing requirements beyond ST (1-2ms between DI/BR) not specified"
- "Z-Wave command class details referenced in appendices but not fully enumerated"