Summary
Furman Contractor Series SmartSequencer with RS-232 control. Controls DELAY outlets (3 banks per unit) via sequenced or individual on/off commands. Supports daisy-chaining multiple units. Serial protocol at 19,200 baud, 8N1, no flow control. No authentication required.
Transport
protocols:
- serial
serial:
baud_rate: 19200
data_bits: 8
parity: none
stop_bits: 1
flow_control: none
auth:
type: none # inferred: no auth procedure in source
Traits
- powerable # SEQ_ON / SEQ_OFF sequence outlet banks
- routable # BANK_ON / BANK_OFF control individual banks
- queryable # ?VOLTAGE, ?CURRENT, ?POWER, ?STATUS, etc.
Actions
- id: seq_on
label: Sequence On
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number (0 = Primary, omit for all units)
command: "!SEQ_ON <sequencer><CR>"
- id: seq_off
label: Sequence Off
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number (0 = Primary, omit for all units)
command: "!SEQ_OFF <sequencer><CR>"
- id: enumerate
label: Enumerate
kind: action
params: []
command: "!ENUMERATE<CR>"
- id: bank_on
label: Bank On
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number
- name: outlet
type: integer
description: "Outlet number (1-3)"
command: "!BANK_ON <sequencer> <outlet><CR>"
- id: bank_off
label: Bank Off
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number
- name: outlet
type: integer
description: "Outlet number (1-3)"
command: "!BANK_OFF <sequencer> <outlet><CR>"
- id: all_off
label: All Off
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number (omit for Primary only)
command: "!ALL_OFF <sequencer><CR>"
- id: events_enable
label: Events Enable
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number
command: "!EVENTS_ENABLE <sequencer><CR>"
- id: events_disable
label: Events Disable
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number
command: "!EVENTS_DISABLE <sequencer><CR>"
- id: reset
label: Reset
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number
command: "!RESET <sequencer><CR>"
- id: clear_per
label: Clear Percent
kind: action
params:
- name: sequencer
type: integer
description: Sequencer number
command: "!CLEAR_PER <sequencer><CR>"
Feedbacks
- id: seq_on_done
label: Sequence On Done
type: event
response: "$SEQ_ON_DONE<CR>"
- id: seq_off_done
label: Sequence Off Done
type: event
response: "$SEQ_OFF_DONE<CR>"
- id: ack_response
label: Acknowledgement
type: event
response: "$ACK <sequencer>,<command><CR>"
- id: seq_change
label: Sequence Change
type: event
description: Issued during reset when Secondary temporarily unreachable
response: "$ACK <sequencer>,SEQ_CHANGE"
Variables
- id: voltage
label: Voltage
type: number
unit: V
query: "?VOLTAGE <sequencer><CR>"
response: "$ACK <sequencer> VOLTAGE=<value><EOT>"
- id: current
label: Current
type: number
unit: A
query: "?CURRENT <sequencer><CR>"
response: "$ACK <sequencer> CURRENT=<value><EOT>"
- id: power
label: Power
type: number
unit: W
query: "?POWER <sequencer><CR>"
response: "$ACK <sequencer> WATTS=<value><EOT>"
- id: power_va
label: Power VA
type: number
unit: VA
query: "?POWER_VA <sequencer><CR>"
response: "$ACK <sequencer> VA=<value><EOT>"
- id: power_factor
label: Power Factor
type: number
query: "?PF <sequencer><CR>"
response: "$ACK <sequencer> PF=<value><EOT>"
- id: device_id
label: Device ID
type: string
query: "?ID <sequencer><CR>"
response: "$ACK <sequencer> ID FURMAN -> Brand <brand> CN-<model> -> Model <serial> -> Serial number <firmware> -> Firmware revision <EOT>"
- id: settings
label: Settings
type: object
query: "?SETTINGS <sequencer><CR>"
response: "$ACK <sequencer> SETTINGS POT ADJ=<value> -> POT Setting DIP MAX DELAY=<value> -> DIP 1-3 setting TOTAL DELAY=<value> -> Total delay setting DIP MODE=<value> -> DIP 7 Position DIP SEQ=<value> -> DIP 8 Position DIP ALARM=<value> -> State of Force Off pins DIP EVS=<value> -> DIP 9 Position KEY=<value> -> Key Switch position <EOT>"
- id: status
label: Status
type: object
query: "?STATUS <sequencer><CR>"
response: "$ACK <sequencer> STATUS SEQ=<value>,<value> -> Sequencer position PROTECT=<value> -> State of protection EVS=<value> -> State of EVS SMP RLY=<value> -> State of SMP relay ALARM=<value> -> State of Force Off input BANK1=<value> -> State of DELAY 1 Output BANK2=<value> -> State of DELAY 2 Output BANK3=<value> -> State of DELAY 3 Output REMOTE=<value> -> State of Legacy remote input PUSHBUTTON=<value> -> State of START SEQUENCE button SECLINK=<value> -> Connection state of Secondary Smartlink UART0 PER=<value> -> % of Primary missed messages UART1 PER=<value> -> % of Secondary missed messages <EOT>"
- id: bank_status
label: Bank Status
type: object
query: "?BANK_STAT <sequencer><CR>"
response: "$ACK <sequencer> BANK_STAT BANK1=<value> -> State of DELAY 1 output BANK2=<value> -> State of DELAY 2 output BANK3=<value> -> State of DELAY 3 output <EOT>"
- id: rollcall
label: Rollcall
type: array
query: "?ROLLCALL<CR>"
response: "$ACK <n>,<model> -> unit <n> $ACK <n>,CN-<model>,LAST -> last unit <EOT>"
Events
# Events are emitted when EVENTS_ENABLE has been sent.
# Event strings start with asterisk (*) per section 1.3.4.
# UNRESOLVED: explicit event list not fully enumerated in source.
# Only SEQ_CHANGE referenced explicitly (section 3.8).
Macros
# No explicit multi-step macros described in source.
Safety
confirmation_required_for: []
interlocks: []
# UNRESOLVED: no safety warnings or interlock procedures in source.
Notes
- Message format: ASCII strings terminated with (0x0D). Incoming also accepts NUL or .
- Receiver buffer limit: 32 characters. Message timeout: 500ms.
- Primary Sequencer requires DIP switch #8 ON and key switch in REMOTE position for serial communication.
- Multiple sequencers can be daisy-chained via SmartLink.
- All units in a chain respond to SEQ_ON/SEQ_OFF without a sequencer argument.
- ?ID response format includes Brand, Model, Serial number, and Firmware revision as key-value pairs.
Provenance
source_domains:
- cdn.shopify.com
- s3-us-west-1.amazonaws.com
- furmanpower.com
- manua.ls
source_urls:
- "https://cdn.shopify.com/s/files/1/0884/1006/3168/files/pdf_CN-1800S-2400S_com-prot.pdf?v=1725473819"
- https://s3-us-west-1.amazonaws.com/corebrands-resources/products/CN-1800S/pdf_CN-1800S-2400S_com-prot.pdf
- https://furmanpower.com/pages/product-manuals
- https://www.manua.ls/furman/smartsequencer-cn-1800s/manual
- "https://cdn.shopify.com/s/files/1/0884/1006/3168/files/pdf_CN-1800S_manual.pdf?v=1723587519"
retrieved_at: 2026-05-19T04:33:34.064Z
last_checked_at: 2026-06-02T22:07:16.263Z
Verification Summary
verdict: verified
checked_at: 2026-06-02T22:07:16.263Z
matched_actions: 10
action_count: 10
confidence: medium
summary: "All 10 spec actions traced to source (dip-safe re-verify). (4 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "explicit event list not fully enumerated in source."
- "no safety warnings or interlock procedures in source."
- "TCP/IP or HTTP interface not documented — only RS-232 described"
- "firmware version range not stated"