RS-232 serial command protocol for Draper MC1 motor controller (used in AeroLift 100 projection screen lifts). Two-way communication at 9600 baud, ASCII framed by * header and ; (or CR) terminator. Supports open/close/stop, calibration, position query, and load-sensing configuration.
Transport
protocols:
- serial
serial:
baud_rate: 9600
data_bits: 8
parity: none
stop_bits: 1
flow_control: software # X-on/X-off per source: buffer half full = X-off, buffer empty = X-on
auth:
type: none # inferred: no auth procedure in source
Traits
- powerable # inferred from open/close commands
- queryable # inferred from "r" position query
Actions
# Command format: *<subsystem><admin><command><channel><time>;
# Subsystem: 02-7 BUS, 7-99 Radio, 0 = ALL
# Channel: 00-60 (00 = ALL, 60 = cut strap ALL)
# Time: 000-999 in 1/20 sec (000 = forever; omit = 2 sec for motion, 1/4 sec for stop/program)
# Case insensitive.
- id: lower_screen
label: Lower Screen (Open)
kind: action
command: "*{subsystem}{o}{channel}{time};"
params:
- name: subsystem
type: integer
description: "02-7 BUS, 7-99 Radio, 0 = ALL"
- name: channel
type: integer
description: "00-60; 00 = ALL, 60 = cut strap ALL"
- name: time
type: integer
description: "000-999 in 1/20 sec; 000 = forever; omit for 2 sec default"
- id: raise_screen
label: Raise Screen (Close)
kind: action
command: "*{subsystem}{c}{channel}{time};"
params:
- name: subsystem
type: integer
description: "02-7 BUS, 7-99 Radio, 0 = ALL"
- name: channel
type: integer
description: "00-60; 00 = ALL, 60 = cut strap ALL"
- name: time
type: integer
description: "000-999 in 1/20 sec; 000 = forever; omit for 2 sec default"
- id: stop_motion
label: Stop Motion
kind: action
command: "*{subsystem}{s}{channel};"
params:
- name: subsystem
type: integer
description: "02-7 BUS, 7-99 Radio"
- name: channel
type: integer
description: "Optional for stop; ignored if present"
- id: program
label: Program
kind: action
command: "*{subsystem}{p}{channel};"
params:
- name: subsystem
type: integer
description: "02-7 BUS, 7-99 Radio"
- name: channel
type: integer
description: "Channel number to program"
- id: program_accessor
label: Program Accessor
kind: action
command: "*{subsystem}{a}{channel};"
params:
- name: subsystem
type: integer
description: "02-7 BUS, 7-99 Radio"
- name: channel
type: integer
description: "Channel number"
- id: quit_forever
label: Quit Sending (stop forever command)
kind: action
command: "*{subsystem}{q}{channel};"
params:
- name: subsystem
type: integer
description: "02-7 BUS, 7-99 Radio"
- name: channel
type: integer
description: "Channel number"
- id: position_query
label: Position Query
kind: query
command: "*{subsystem}{r}{channel};"
params:
- name: subsystem
type: integer
description: "02-7 BUS, 7-99 Radio; 0 = ALL (excludes radio)"
- name: channel
type: integer
description: "Channel number"
- id: version_query
label: Version Query
kind: query
command: "*V;"
params: []
- id: admin_radio
label: Administer Port 7 as Radio
kind: action
command: "*R;"
params: []
- id: admin_bus
label: Administer Port 7 as BUS
kind: action
command: "*B;"
params: []
- id: calibrate_motor
label: Calibrate Motor
kind: action
command: "*p01;*c10;*o10;"
params: []
notes: "Per source: programs, closes to upper limit, opens to lower limit, returns to lower limit. Motor becomes calibrated."
- id: factory_reset
label: Factory Reset
kind: action
command: "*p00;*c00;*c01;*o01;*s;"
params: []
notes: "Per source: button cannot be held, use this command string to reset all settings to factory default."
- id: set_min_load
label: Set Minimum Load Threshold
kind: action
command: "C18 O{x} O{y}"
params:
- name: x
type: integer
description: "Ox; O5-O9 ignored as out of range; O10 = y=0 shortcut"
- name: y
type: integer
description: "Oy; ignored if 0"
notes: "Source documents this as IR-style load-sense command, not RS-232 frame. Listed for completeness."
- id: set_stall_threshold
label: Set Stall Load Threshold
kind: action
command: "C19 O{x} O{y}"
params:
- name: x
type: integer
description: "Ox; O5-O9 ignored as out of range; O10 = y=0 shortcut"
- name: y
type: integer
description: "Oy; ignored if 0"
notes: "IR-style load-sense command. Nudge with C19 O11 (up) or C19 O12 (down)."
- id: set_specific_stop
label: Set Specific Stop Channel
kind: action
command: "C22 O{N}"
params:
- name: N
type: integer
description: "Channel number to bind as specific-stop for this motor"
notes: "IR-style. Serial users can use plain 's' command on any channel."
Feedbacks
- id: powerup_message
description: Sent on power-up, before command traffic
payload: '"version, X-on" # version string followed by X-on (0x11)'
- id: position_report
description: Periodic position report, also on "r" query
payload: "*nnRpp; # nn = main channel, pp = percent away from reference (0-99, 0=at reference, 99=opposite limit)"
- id: position_unknown_uncalibrated
description: Response to "r" query when position unknown because not yet calibrated
payload: "*nnRN;"
- id: position_unknown
description: Response to "r" query when position unknown for other reason
payload: "*nnRU;"
- id: ack_good
description: Command formatted correctly and not "r" or "s"
payload: "G;"
- id: nack_format
description: Command not formatted correctly
payload: "U;"
- id: nack_uncalibrated
description: "m" command cannot be executed because motor is uncalibrated
payload: "X;"
- id: version_response
description: Response to "V" query
payload: "2.0;"
- id: buffer_overflow
description: 120-byte buffer overflowed, all data purged
payload: "O followed by X-on (0x11)"
- id: flow_control_xoff
description: Buffer half full; sender must pause
payload: "X-off (0x13, Ctrl-S)"
- id: flow_control_xon
description: Buffer empty; sender may resume (only if X-off was sent)
payload: "X-on (0x11, Ctrl-Q)"
Variables
# UNRESOLVED: load-sensing thresholds (min load, stall) are configured by C18/C19
# commands (see Actions). No read-back query documented in source.
Events
- id: powerup
description: "On power-up, controller sends 'version, X-on' before any command traffic."
- id: motion_complete
description: "While motor moves, controller emits periodic position reports. Report reflects position at moment end-of-command character is received, not at time of report generation."
# See Feedbacks.position_report
Macros
# Multi-step sequences documented in source.
- id: calibrate_motor
description: Calibrate motor to its limits
steps:
- "*p01; # program"
- "*c10; # close to upper limit (10 = 0.5 sec pulse)"
- "*o10; # open to lower limit"
- id: factory_reset
description: Reset all settings to factory default
steps:
- "*p00;"
- "*c00;"
- "*c01;"
- "*o01;"
- "*s; # stop"
notes: "Source: 'button cannot be held, so to reset everything to factory default send this sequence.'"
- id: lower_screen_test
description: Initial connection test from source
steps:
- "*o01; # lower screen; verify motion + report received"
Safety
confirmation_required_for: []
interlocks:
- "Load sensing: motor stops if current exceeds stall threshold for 1/4 sec, or stays below min load for 1/2 sec after start."
- "Source warning: when IR command is being sent, serial commands may be lost; when serial command is received, IR command may be lost."
# UNRESOLVED: no electrical ratings, stall current defaults, or installation interlocks in source.
Notes
- Message length: 2-10 characters, typically 6.
- Case insensitive:
o==O, etc. - Time field default: omitted = 2 sec for motion commands, 1/4 sec for stop/program. Time between buffered commands = 0.5 sec (0.1 sec after a stop). Max timed pulse = 50 sec.
- Position accuracy: percentage may have up to 2% error.
- Address filtering: "no response" if
r,m, orscommand not addressed to this unit. - Radio mode: subsystem 7-99 requires RFTM plugged into port 7 jack, powered by DCPM.
- Report timing: position report reflects state at end-of-command, not at report emission time.
- Calibration prerequisite: motor must be calibrated (
*p01;*c10;*o10;) before position queries return meaningful percentages. - Stall tuning procedure in source: measure running current or read motor rating label, enter as C19 threshold, run to stall point, verify MC1 shuts off 1/4 sec after stall. If MC1 keeps running, threshold too high; nudge down (C19 O12). If motor stops mid-travel, too sensitive; nudge up (C19 O11).
- C18/C19/C22 commands are documented as IR-style load-sense configuration, not the framed RS-232 protocol. Included for completeness; their framing differs from
*...;syntax.
Provenance
source_domains:
- draperinc.com
source_urls:
- "https://www.draperinc.com/documentdownload.aspx?path=ProjectionScreens/Instructions&file=SerialComm-RS232_Inst.pdf"
retrieved_at: 2026-05-14T15:35:22.030Z
last_checked_at: 2026-06-02T21:41:35.437Z
Verification Summary
verdict: verified
checked_at: 2026-06-02T21:41:35.437Z
matched_actions: 15
action_count: 15
confidence: medium
summary: "All 15 spec actions matched verbatim in source with correct transport parameters (9600 baud, 8 data bits, no parity, 1 stop bit, software flow control). (7 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "no port number, voltage, or current specs in source."
- "load-sensing thresholds (min load, stall) are configured by C18/C19"
- "no electrical ratings, stall current defaults, or installation interlocks in source."
- "no RS-232 port number (D-sub pinout / DB9/DB25) stated."
- "no voltage, current draw, or power supply specs in source."
- "firmware version compatibility range not stated; controller reports \"2.0\" on V query."
- "factory-default values for min load and stall thresholds not stated."