Summary
The CoolAutomation CooLinkBridge exposes a text-based RS-232 control protocol (referred to in the source as the "Cool Master" protocol) used to command and query HVAC indoor units addressed by 3-character UIDs. This spec covers the command set, response format, and serial transport parameters documented in the vendor reference.
Transport
# Source explicitly documents RS-232 only (section 2). No TCP/IP, HTTP, or
# authentication material is present in the source.
protocols:
- serial
serial:
baud_rate: 9600
data_bits: 8
parity: none
stop_bits: 1
flow_control: none
auth:
type: none # inferred: no auth procedure in source
Traits
# - powerable # inferred from on/off/allon/alloff command examples
# - queryable # inferred from stat/stat2/stat3/stat4/query command examples
# - levelable # inferred from temp/fspeed/swing command examples
Actions
- id: alloff
label: All Indoor Units Off
kind: action
command: "alloff"
params: []
- id: allon
label: All Indoor Units On
kind: action
command: "allon"
params: []
- id: boot
label: Enter Bootloader Mode
kind: action
command: "boot"
params: []
- id: cool
label: Set Unit Mode To Cool
kind: action
command: "cool {uid}"
params:
- name: uid
type: string
description: 3-character indoor unit address (e.g. 102)
- id: dry
label: Set Unit Mode To Dry
kind: action
command: "dry {uid}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- id: heat
label: Set Unit Mode To Heat
kind: action
command: "heat {uid}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- id: auto_mode
label: Set Unit Mode To Auto
kind: action
command: "auto {uid}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- id: fan_mode
label: Set Unit Mode To Fan
kind: action
command: "fan {uid}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- id: filt
label: Reset Filter Sign
kind: action
command: "filt {uid}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- id: fspeed
label: Set Fan Speed
kind: action
command: "fspeed {uid} {speed}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- name: speed
type: string
description: "Fan speed letter: l (low), m (medium), h (high), a (auto), t (top). Supported letters depend on CoolMaster model."
- id: off
label: Turn Unit Off
kind: action
command: "off {uid} {output?}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- name: output
type: integer
description: "Optional PAC-YG66 digital output number 1..6 (CoolMaster 4000M v2.5.6+ only)"
- id: on
label: Turn Unit On
kind: action
command: "on {uid} {output?}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- name: output
type: integer
description: "Optional PAC-YG66 digital output number 1..6 (CoolMaster 4000M v2.5.6+ only)"
- id: set
label: Query Or Set Configuration
kind: action
command: "set {option} {value?}"
params:
- name: option
type: string
description: "Configuration option. Read-only: S/N, version, CS count, TO count, Collisio, NA Count, MB CRC. Read/Write: myid, echo, baud, deg (C|F), slink, master, lcd, simul, modaddr, ignore."
- name: value
type: string
description: "Option value. Omitted for query. For deg use C or F. For echo use 0 or 1. For baud use 1200/2400/4800/9600/18200/38400/57600/115200."
- id: simul
label: Simulate Indoor Units
kind: action
command: "simul {n}"
params:
- name: n
type: integer
description: "Number of indoor units to simulate. 0 to exit simulation mode."
- id: stat
label: Get Indoor Unit Status
kind: query
command: "stat {uid?}"
params:
- name: uid
type: string
description: "Optional 3-character indoor unit address. Omit for all units."
- id: stat2
label: Get Indoor Unit Status With Filter Sign
kind: query
command: "stat2 {uid?}"
params:
- name: uid
type: string
description: "Optional 3-character indoor unit address. Omit for all units."
- id: stat3
label: Get Indoor Unit Status (Integer Temperature)
kind: query
command: "stat3 {uid?}"
params:
- name: uid
type: string
description: "Optional 3-character indoor unit address. Omit for all units."
- id: stat4
label: Get Indoor Unit Status With Thermostat
kind: query
command: "stat4 {uid?}"
params:
- name: uid
type: string
description: "Optional 3-character indoor unit address. Omit for all units."
- id: query
label: Query Single Parameter
kind: query
command: "query {uid} {parameter}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- name: parameter
type: string
description: "Parameter letter: o (on/off), m (mode), f (fan speed), t (set temp), e (failure code), a (ambient temp), h (set temp 0.01 precision), s (swing)"
- id: swing
label: Set Swing Position
kind: action
command: "swing {uid} {position}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- name: position
type: string
description: "a (auto), h (horizontal), 3 (30 deg), 4 (45 deg), 6 (60 deg), v (vertical)"
- id: temp
label: Set Temperature
kind: action
command: "temp {uid} {temperature}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- name: temperature
type: string
description: "Decimal number, optionally prefixed with + or - for relative delta. With 0.01 precision suffix (XX.xx) for high-resolution set."
- id: group
label: Group Units
kind: action
command: "group {uid_master} {uid}"
params:
- name: uid_master
type: string
description: Master unit UID; second unit will follow this unit's settings. Omit (or use delall) to list/delete groups.
- name: uid
type: string
description: "Follower unit UID. Use literal delall to delete all groups. Power reset required to take effect."
- id: vam
label: VAM Unit Mode And Fan
kind: action
command: "vam {uid} {letter}"
params:
- name: uid
type: string
description: 3-character VAM unit address
- name: letter
type: string
description: "a (Auto Mode), b (Bypass), x (Heat Exchange), n (Normal), l (Low Fan), L (Low Fan w/ Fresh-Up), h (High Fan), H (High Fan w/ Fresh-Up), s (Super High Fan), A (Auto Fan). Compatibility per CoolMaster model."
- id: lock
label: Lock Wall Controller
kind: action
command: "lock {uid} {operation?}"
params:
- name: uid
type: string
description: 3-character indoor unit address
- name: operation
type: string
description: "Omit to query. Use + or - to lock/unlock all. Use +/- followed by o (on/off), m (mode change), s (set temp), n (on, 1000D only), t to toggle specific operations. Multiple +/- tokens allowed."
- id: wh
label: Water Heating Unit Mode
kind: action
command: "wh {uid} {letter}"
params:
- name: uid
type: string
description: 3-character water heating unit address (CoolMaster 4000M only)
- name: letter
type: string
description: "h (Heating), e (ECO), w (Hot Water), a (Anti-freeze)"
- id: unknown_command_response
label: Unknown Command Error
kind: feedback
command: "Unknown command"
- id: bad_parameters_response
label: Bad Parameters Error
kind: feedback
command: "Bad parameters"
Feedbacks
# Responses to the stat family of queries. Format is positional and depends
# on which stat variant was issued. Values below reflect stat (the base form).
- id: stat_response
type: object
description: |
One line per indoor unit. Positions: 0-2 centralized address (NNN);
4-6 on/off (ON|OFF); 8-10 set temperature (NNC, NNNF in Fahrenheit);
12-17 room temperature (NN,NNC); 19-22 fan speed (Low|Med|High|Auto|Top);
24-27 mode (Cool|Heat|Fan|Dry|Auto, with AutC/AutH for auto-cooling/auto-heating);
29-32 status (OK or Xn/Xnn/nnnn failure code).
fields:
- name: address
type: string
- name: on_off
type: enum
values: [ON, OFF]
- name: set_temp
type: string
- name: room_temp
type: string
- name: fan_speed
type: enum
values: [Low, Med, High, Auto, Top]
- name: mode
type: enum
values: [Cool, Heat, Fan, Dry, Auto, AutC, AutH]
- name: status
type: string
# stat2 adds a trailing 0/1 filter-reset-sign column.
# stat3 drops the fractional part of room temperature and adds the filter sign.
# stat4 extends stat3 with a trailing THERMOSTAT_ON column (1=On, 0=Off).
# PAC-YG66 (digital I/O, CoolMaster 4000M v2.5.6+) response:
# "NNN DIG IN:XXXXXX OUT:XXXXXXX OK" - 6 digital inputs and 6/7 digital outputs.
# PAC-YG63 (analog I/O, CoolMaster 4000M v2.5.6+) response:
# "NNN ANA NNN.n NNN.n OK" - two analog input values with 0.1 precision.
#
# query responses are single values; see the `query` action's parameter table.
Variables
# Read/write CoolMaster configuration options exposed by the `set` command.
# Values are read with `set <option>` (no value) and written with
# `set <option> <value>`. Some options are read-only.
- id: myid
type: string
access: read_write
description: Own centralized address (hex 0A, etc.)
- id: echo
type: integer
access: read_write
values: [0, 1]
description: Command echo. 0=disable, 1=enable.
- id: baud
type: integer
access: read_write
values: [1200, 2400, 4800, 9600, 18200, 38400, 57600, 115200]
description: "RS-232 baud rate. Default 9600. Change takes effect only after power reset."
- id: deg
type: string
access: read_write
values: [C, F]
description: Temperature scale. C=Celsius, F=Fahrenheit.
- id: slink
type: string
access: read_write
values: [O, N]
description: A/C line link type for CoolMaster 8000I(MH). O=Old, N=New.
- id: master
type: integer
access: read_write
values: [0, 1]
description: "1=Master, 0=Slave. For CoolMaster 6000L/1000D."
- id: lcd
type: string
access: read_write
description: LCD size.
- id: simul
type: integer
access: read_write
description: "Number of indoor units permanently simulated. Non-zero keeps simulation active after reset."
- id: modaddr
type: string
access: read_write
description: "Modbus address (Coolgate only)."
- id: ignore
type: string
access: read_write
description: "Ignore flags. r = ignore Modbus Illegal Data Address (Coolgate only)."
- id: serial_number
type: string
access: read_only
description: CoolMaster unit serial number.
- id: version
type: string
access: read_only
description: Firmware version.
- id: cs_count
type: integer
access: read_only
description: Check sum errors counter.
- id: to_count
type: integer
access: read_only
description: Timeout errors counter.
- id: collision_count
type: integer
access: read_only
description: Collision counter.
- id: na_count
type: integer
access: read_only
description: NAK counter.
- id: mb_crc
type: integer
access: read_only
description: Modbus bad CRC counter (Coolgate only).
Events
# The bridge emits a `>` prompt character when ready to accept a new command.
# No other unsolicited notifications are documented in the source.
- id: prompt_ready
payload: ">"
description: Bridge is ready to accept a new command.
Macros
# Grouping is the only multi-step / relational operation explicitly described.
# Source: section 4.1.21. Grouping only takes effect after a power reset of
# the bridge.
- id: group_units
description: Make a follower UID mirror all settings of a master UID.
steps:
- "lock {follower_uid} + # optional: lock follower's wall controller to prevent manual override"
- "group {master_uid} {follower_uid}"
- "Power-reset the bridge to activate the group."
- id: ungroup_all
description: Remove all group bindings.
steps:
- "group delall"
- "Power-reset the bridge to deactivate the groups."
Safety
confirmation_required_for: []
interlocks: []
# UNRESOLVED: no safety warnings, interlock procedures, or power-on sequencing
# requirements are stated in the source. The only sequencing note is that
# `group` and `baud` changes take effect only after a power reset of the bridge.
Notes
- Prompt: The bridge emits a
>prompt character when ready. Commands are case-sensitive, must not contain leading/trailing spaces, and use a single space as the only separator between command name and parameters. - Termination: Commands are terminated by CR LF (
\r\n) or a single CR (\r). Responses (except the prompt) are terminated by CR LF. - Exit codes: Successful commands return
OK. Thestatfamily also returns a per-unit status ofOKor a failure code (Xn,Xnn,nnnn). - Address model: UIDs are 3 characters — first char is system number 0-9 or A-F (or
Zfor centralized address mode), followed by two hex/decimal digits. Supported UID ranges vary by CoolMaster model (see source section 3.2). - Backward compatibility: The
statcommand is documented as obsolete;stat2/stat3/stat4are preferred. Unit numbers 0-15 may also be written as hex pairs (e.g.10A= centralized 1-15); source discourages this. - Mode status reporting: In
Automode,statmay reportAuto,AutC(auto-cooling), orAutH(auto-heating). - Filter sign: Only
stat2/stat3/stat4include the filter-reset-sign column. - Source/target mismatch: The refined source documents the Cool Master RS-232 protocol. The CooLinkBridge product name was supplied separately; if a CooLinkBridge-specific TCP/IP or REST surface exists, it is not captured in this source and is left as UNRESOLVED.
Provenance
source_domains:
- coolautomation.com
- support.coolautomation.com
source_urls:
- https://coolautomation.com/Lib/doc/prm/CoolAutomation-PRM-CoolMaster-v4.06.pdf
- https://support.coolautomation.com/hc/en-us/articles/4417614903953-CoolMaster-PRM-Programmers-Reference-Manual
- https://coolautomation.com/Lib/doc/CoolMasterNet/prm/CoolMasterNet-PRM-v0.9.pdf
- https://coolautomation.com/products/coolinkbridge/
- https://coolautomation.com/products/api/
retrieved_at: 2026-04-29T21:22:41.675Z
last_checked_at: 2026-06-02T21:41:17.400Z
Verification Summary
verdict: verified
checked_at: 2026-06-02T21:41:17.400Z
matched_actions: 27
action_count: 27
confidence: medium
summary: "All 27 spec actions matched literally in source command reference; transport parameters verified verbatim; bidirectional coverage complete. (3 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "refined source documents the Cool Master command set and RS-232 transport. The CooLinkBridge product line typically also exposes a TCP/IP interface, but no TCP/IP, port, HTTP, REST, or authentication details appear in the source. Treat the device as RS-232-only per the source until contradicted."
- "no safety warnings, interlock procedures, or power-on sequencing"
- "TCP/IP, port, HTTP, REST, authentication, and any cloud/Coohub-specific endpoints for the CooLinkBridge are not described in this source. The baud-rate list in `set` includes 18200 (likely a typo for 19200) — preserved verbatim from the source."