Summary
The ControlByWeb X417 is an industrial I/O module in the X-400 Series. This spec covers its TCP/IP control surface, including HTTP GET (state.xml / state.json / customState endpoints), Modbus/TCP slave operation on port 502, SNMP v1/v2c/v3 monitoring, and MQTT 3.1.1 publish/subscribe (including Sparkplug B).
Transport
protocols:
- tcp
- http
addressing:
port: 80 # source example: http://192.168.1.2/state.xml; also references ":8000" when port changed
auth:
type: basic # source: "Authorization: Basic bm9uZTp3ZWJyZWxheQ==" for requests when the User account is enabled; syslog.txt requires setup credentials
Traits
- queryable # inferred: state.xml/json read endpoints, Modbus Read functions
- powerable # inferred: relay on/off/pulse commands
- routable # inferred: not explicitly routing I/O; omitted
Actions
- id: read_state_xml
label: Read state.xml
kind: query
command: "GET /state.xml HTTP/1.1\r\n\r\n"
params: []
- id: read_state_json
label: Read state.json
kind: query
command: "GET /state.json HTTP/1.1\r\n\r\n"
params: []
- id: set_register_via_http
label: Set Register 1 (HTTP)
kind: action
command: "GET /state.xml?register1=25 HTTP/1.1\r\n\r\n"
params:
- name: register1
type: number
description: "Register value (example: 25; floats supported per source: 10.5)"
- id: relay1_off
label: Turn Relay 1 OFF
kind: action
command: "GET /state.xml?relay1=0 HTTP/1.1\r\n\r\n"
params: []
- id: relay1_on
label: Turn Relay 1 ON
kind: action
command: "GET /state.xml?relay1=1 HTTP/1.1\r\n\r\n"
params: []
- id: relay1_pulse
label: Pulse Relay 1 (preset duration)
kind: action
command: "GET /state.json?relay1=2 HTTP/1.1\r\n\r\n"
params: []
- id: relay1_pulse_custom
label: Pulse Relay 1 (custom duration, seconds)
kind: action
command: "GET /state.json?pulseTime1=5&relay1=2 HTTP/1.1\r\n\r\n"
params:
- name: pulseTime1
type: integer
description: Pulse duration in seconds (pulseTime argument MUST precede relay1=2 per source)
- id: relay2_off
label: Turn Relay 2 OFF
kind: action
command: "GET /state.xml?relay2=0 HTTP/1.1\r\n\r\n"
params: []
- id: relay2_on
label: Turn Relay 2 ON
kind: action
command: "GET /state.xml?relay2=1 HTTP/1.1\r\n\r\n"
params: []
- id: relay2_pulse
label: Pulse Relay 2
kind: action
command: "GET /state.xml?relay2=2 HTTP/1.1\r\n\r\n"
params: []
- id: set_on_time
label: Set onTime1
kind: action
command: "GET /state.xml?onTime1=0 HTTP/1.1\r\n\r\n"
params:
- name: onTime1
type: number
description: Time in seconds since input last came on (resets to 0 or sets value)
- id: set_total_on_time
label: Set totalOnTime1
kind: action
command: "GET /state.xml?totalOnTime1=0 HTTP/1.1\r\n\r\n"
params:
- name: totalOnTime1
type: number
description: Total time in seconds input has been on
- id: set_counter
label: Set counter1
kind: action
command: "GET /state.json?count1=200 HTTP/1.1\r\n\r\n"
params:
- name: count1
type: number
description: Counter value
- id: set_custom_register
label: Set custom-named register
kind: action
command: "GET /customState.xml?myRegister1=10 HTTP/1.1\r\n\r\n"
params:
- name: myRegister1
type: number
description: Value for user-named register (camelCase name from customState.xml)
- id: multi_relay_command
label: Multi-relay command (HTTP)
kind: action
command: "GET /customState.xml?relay1=1&relay2=0 HTTP/1.1\r\n\r\n"
params: []
- id: erase_log_txt
label: Erase log.txt
kind: action
command: "GET /log.txt?erase=1 HTTP/1.1\r\n\r\n"
params: []
- id: erase_syslog_txt
label: Erase syslog.txt
kind: action
command: "GET /syslog.txt?erase=1 HTTP/1.1\r\n\r\n"
params: []
- id: modbus_read_coils
label: Modbus Read Coils (FC01)
kind: query
command: "Modbus FC 0x01 - Read relays and digital I/O (configured as outputs). Start address & quantity from device Modbus map."
params: []
- id: modbus_read_discrete_inputs
label: Modbus Read Discrete Inputs (FC02)
kind: query
command: "Modbus FC 0x02 - Read digital inputs and digital I/O (configured as inputs)."
params: []
- id: modbus_read_holding_registers
label: Modbus Read Holding Registers (FC03)
kind: query
command: "Modbus FC 0x03 - Read Vin, sensors, registers, counters, analog inputs (32-bit floats, register pairs)."
params: []
- id: modbus_write_single_coil
label: Modbus Write Single Coil (FC05)
kind: action
command: "Modbus FC 0x05 - Output value 0x00 (off) or 0xFF (on)."
params:
- name: output_value
type: enum
values: [0x00, 0xFF]
- id: modbus_write_multiple_coils
label: Modbus Write Multiple Coils (FC15)
kind: action
command: "Modbus FC 0x0F - Output value 0x0000-0xFFFF; byte count = quantity/8."
params: []
- id: modbus_write_multiple_registers
label: Modbus Write Multiple Registers (FC16)
kind: action
command: "Modbus FC 0x10 - 32-bit IEEE 754 floats, little- or big-endian per device config; must be even register count."
params: []
- id: modbus_pulse_relay
label: Modbus Pulse Relay (32-bit float seconds; function code UNRESOLVED)
kind: action
command: "" # UNRESOLVED: source conflicts on the pulse function code; no command selected
description: "Pulse Relay 1 by writing a 32-bit float pulse duration in seconds to addresses 512-513 (PLC 40513-40514). Section 2.1.3 explicitly gives Function code 0x16 for this pulse operation, while Section 2.1.9 defines Write Multiple Registers as decimal 16 (0x10). The pulse function code remains UNRESOLVED."
params: []
- id: cloud_state_json
label: "Cloud API: Read state.json"
kind: query
command: "GET https://api.controlbyweb.cloud/{DAT_url}/state.json HTTP/1.1\r\n\r\n"
params: []
- id: cloud_multi_relay
label: "Cloud API: Trigger multiple relays"
kind: action
command: "GET https://api.controlbyweb.cloud/{DAT_url}/state.json?relay1=1&relay2=1 HTTP/1.1\r\n\r\n"
params: []
Feedbacks
- id: relay_state
type: enum
values: [0, 1] # 0=off (coil off), 1=on (coil energized) per source
description: "<relayX> in state.xml/json; also returned as bit-packed Modbus Read Coils response"
- id: digital_input_state
type: enum
values: [0, 1] # 0=off (voltage not applied), 1=on (voltage applied) per source
description: "<digitalInputX> in state.xml/json; also Modbus Read Discrete Inputs"
- id: vin
type: number
description: Scaled internal Vin measurement (always present in state.xml/json per source)
- id: analog_input
type: number
description: "<analogInputX> value of analog input X"
- id: one_wire_sensor
type: number
description: "x.x = sensor not read; numeric value (e.g. 77.3) with optional showUnits=1 for units"
- id: register_value
type: number
description: "<registerX> value of register X"
- id: count_value
type: number
description: "<countX> count value associated with input X"
- id: frequency_value
type: number
description: "<frequencyX> frequency associated with input X"
- id: on_time
type: number
description: "<onTimeX> seconds since input last came on"
- id: total_on_time
type: number
description: "<totalOnTimeX> total seconds input has been on"
- id: utc_time
type: integer
description: "Current UTC time in seconds since 1970-01-01"
- id: timezone_offset
type: integer
description: "Offset to apply to utcTime for local time"
- id: serial_number
type: string
description: "Device MAC/serial, format 00:0C:C8:xx:xx:xx"
Variables
- id: register
type: number
description: "Writable register; settable via state.xml?register1={value} or Modbus FC 0x10"
writable: true
Events
- id: snmp_trap_relay
description: "SNMP trap sent when a relay changes state (per source §3.1.3)"
- id: snmp_trap_sensor
description: "SNMP trap when a configured sensor value is reached"
- id: snmp_trap_vin
description: "SNMP trap when supply voltage is out of desired range"
- id: remote_services_state
description: "When Remote Services enabled and a logic event triggers send-state, the state.xml is sent over the open TCP V1 connection (per source §5.1)"
Macros
# UNRESOLVED: source does not describe named multi-step macro sequences on the X417 itself
# (Conditional/Scheduled tasks exist in firmware but command details are not in this excerpt)
Safety
confirmation_required_for: []
interlocks: []
# UNRESOLVED: no safety warnings, interlocks, or power-on sequencing documented in this excerpt
Notes
- Source explicitly references the X-400 Series family. The X417 is one model in that family; some examples (relay numbers, vin value) are illustrative rather than X417-specific.
- HTTP requests for state.xml require Basic authentication when the User account is enabled; log.txt also requires the user password when that account is enabled. Access to syslog.txt requires the setup username and password. The source illustrates Basic authentication with
none:webrelay(Base64bm9uZTp3ZWJyZWxheQ==); it does not identify those credentials as defaults. Default HTTP credentials are UNRESOLVED. - Modbus/TCP uses port 502 and is disabled when the User account is enabled (Modbus has no password mechanism).
- Modbus connection times out after 50 seconds of inactivity; send a periodic read to keep it open. Two TCP sockets available.
- MQTT supports v3.1.1 and Sparkplug B. Community strings (SNMP v1/v2c) default to
webrelay. - Pulse relay:
pulseTimeargument MUST precederelay1=2in the HTTP query string. - Modbus pulse function code is UNRESOLVED: the PLC addressing example specifies
0x16, while the Write Multiple Registers definition specifies decimal 16 (0x10). The pulse action retains the documented addresses and payload, with an empty command pending resolution of this source contradiction. - The ControlByWeb Cloud "Remote Services" V2 is reserved for ControlByWeb.Cloud and not for general use.
Provenance
source_domains:
- controlbyweb.com
source_urls:
- https://controlbyweb.com/wp-content/uploads/2025/05/cbw-integration-and-protocols-manual.pdf
- https://controlbyweb.com/wp-content/uploads/2025/05/400-series-users-manual.pdf
- https://controlbyweb.com/wp-content/uploads/2024/01/x417-qsg_v1.0.pdf
- https://controlbyweb.com/wp-content/uploads/2025/04/x-417-v19.7.pdf
- https://controlbyweb.com/support/
retrieved_at: 2026-06-30T15:14:30.854Z
last_checked_at: 2026-10-07T11:12:56.488Z
Verification Summary
verdict: verified
checked_at: 2026-10-07T11:12:56.488Z
matched_actions: 26
action_count: 26
confidence: medium
summary: "All 26 action units match the source, transport values are supported, and only log.txt and syslog.txt reads are unrepresented; the Modbus pulse code conflict is declared as UNRESOLVED. (8 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "GET /log.txt"
- "GET /syslog.txt"
- "RS-232C was flagged as the known protocol, but no RS-232 / serial material appears in the source document. Only TCP/IP-based protocols are documented."
- "Modbus/TCP slave port 502 stated in source. SNMP, MQTT, and Cloud ports not specified."
- "source conflicts on the pulse function code; no command selected"
- "only a subset of relays (1, 2) and one register shown in source tables. X-400 Series devices may expose additional local I/O numbers; the full Modbus address map must be retrieved from the device's setup pages (per source: \"View Modbus Address Table\")."
- "source does not describe named multi-step macro sequences on the X417 itself"
- "no safety warnings, interlocks, or power-on sequencing documented in this excerpt"
- "the PLC addressing example specifies `0x16`, while the Write Multiple Registers definition specifies decimal 16 (`0x10`). The pulse action retains the documented addresses and payload, with an empty command pending resolution of this source contradiction."
- "known protocol was specified as RS-232C, but the source document contains no RS-232/serial material — only TCP/IP-based protocols (HTTP, Modbus/TCP, SNMP, MQTT). No baud rate, data bits, parity, or stop bits documented."