Summary
ControlByWeb Quick Connect is a network-attached relay/IO module. Spec covers the integration protocols documented for the 400/X-600 Series family: HTTP GET (state.xml/state.json/customState.xml/customState.json, log files), Modbus/TCP slave, SNMP v1/v2c/v3, MQTT v3.1.1 + Sparkplug B, Remote Services (TCP), and ControlByWeb.Cloud DAT URLs.
Transport
protocols:
- http
- tcp
- mqtt
- snmp
addressing:
# HTTP serves state.xml, state.json, customState.xml, customState.json, log.txt, syslog.txt.
# Port 80 default; port 8000 shown in example when changed ("not port 80").
port: 80
base_url: "http://{device-ip}"
# Modbus/TCP port: source explicitly states port 502 (configurable).
modbus_port: 502
auth:
type: basic # inferred: source shows HTTP Basic auth (Base64 "Authorization: Basic ...") and notes Modbus disabled when user account enabled
Note on omitted protocol sub-blocks: Source describes the protocols above but does not give serial parameters, UDP port, or OSC details. The HTTP/MQTT/SNMP sub-keys not explicitly listed in the source are omitted; do not infer values.
Traits
# - powerable (relay on/off commands present - relayX=0/1)
# - levelable (register values numeric; analog inputs read/writable)
# - routable (no input/output routing matrix; omitted)
# - queryable (state.xml/json read; Modbus read functions 01/02/03; SNMP Get)
Actions
# HTTP GET state read
- id: get_state_xml
label: Read state.xml
kind: query
command: "GET /state.xml HTTP/1.1\r\n\r\n"
transport: http
params: []
- id: get_state_json
label: Read state.json
kind: query
command: "GET /state.json HTTP/1.1\r\n\r\n"
transport: http
params: []
- id: get_custom_state_xml
label: Read customState.xml
kind: query
command: "GET /customState.xml HTTP/1.1\r\n\r\n"
transport: http
params: []
- id: get_custom_state_json
label: Read customState.json
kind: query
command: "GET /customState.json HTTP/1.1\r\n\r\n"
transport: http
params: []
# Relay control via state.xml/json. Source documents relayX=0 (off), =1 (on), =2 (pulse).
# X replaced by local I/O number.
- id: relay_off
label: Turn Relay Off
kind: action
command: "GET /state.xml?relay{X}=0 HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local relay number
- id: relay_on
label: Turn Relay On
kind: action
command: "GET /state.xml?relay{X}=1 HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local relay number
- id: relay_pulse
label: Pulse Relay (preset duration)
kind: action
command: "GET /state.xml?relay{X}=2 HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local relay number
# Pulse with explicit duration. source states pulseTimeX MUST precede relayX=2.
- id: relay_pulse_time
label: Pulse Relay for N seconds
kind: action
command: "GET /state.json?pulseTime{X}={seconds}&relay{X}=2 HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local relay number
- name: seconds
type: integer
description: Pulse duration in seconds (example shows 5 and 15)
# Counter / on-time setters
- id: set_counter
label: Set counter value
kind: action
command: "GET /state.json?count{X}={value} HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local counter number
- name: value
type: integer
description: New counter value (example: 200)
- id: set_on_time
label: Set onTime value
kind: action
command: "GET /state.xml?onTime{X}={seconds} HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local input number
- name: seconds
type: integer
description: onTime value (example: 0, 5)
- id: set_total_on_time
label: Set totalOnTime value
kind: action
command: "GET /state.xml?totalOnTime{X}={seconds} HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local input number
- name: seconds
type: integer
description: totalOnTime value (example: 0, 5)
# Register set (state.xml path with example; customState path also valid)
- id: set_register
label: Set register value
kind: action
command: "GET /state.xml?register{X}={value} HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local register number
- name: value
type: number
description: New register value (example: 10.5)
- id: set_register_customstate
label: Set register via customState (named)
kind: action
command: "GET /customState.xml?myRegister{X}={value} HTTP/1.1\r\n\r\n"
transport: http
params:
- name: X
type: integer
description: Local register number
- name: value
type: number
description: New register value (example: 10)
- name: name
type: string
description: User-configured name; XML tag becomes camelCase version (e.g. "My Register 1" -> myRegister1)
# Multiple-command aggregation (source example)
- id: relay_set_multiple
label: Set multiple relays in one request
kind: action
command: "GET /state.json?relay1=1&relay2=0 HTTP/1.1\r\n\r\n"
transport: http
params: []
# Log file access
- id: get_data_log
label: Read log.txt
kind: query
command: "GET /log.txt HTTP/1.1\r\n\r\n"
transport: http
params: []
- id: erase_data_log
label: Erase log.txt
kind: action
command: "GET /log.txt?erase=1 HTTP/1.1\r\n\r\n"
transport: http
params: []
- id: get_syslog
label: Read syslog.txt
kind: query
command: "GET /syslog.txt HTTP/1.1\r\n\r\n"
transport: http
params: []
- id: erase_syslog
label: Erase syslog.txt
kind: action
command: "GET /syslog.txt?erase=1 HTTP/1.1\r\n\r\n"
transport: http
params: []
# Modbus/TCP slave. Source explicitly documents function codes 01,02,03,05,15,16 plus PLC addressing.
# MBAP header + PDU encoding per Modbus spec; payload here is the Modbus PDU context.
- id: modbus_read_coils
label: Modbus Read Coils (function 0x01)
kind: query
command: "MODBUS/TCP function=0x01 address={start} quantity={count}"
transport: modbus_tcp
port: 502
params:
- name: start
type: integer
description: Starting coil address (see Modbus map in setup)
- name: count
type: integer
description: Coil quantity
- id: modbus_read_discrete_inputs
label: Modbus Read Discrete Inputs (function 0x02)
kind: query
command: "MODBUS/TCP function=0x02 address={start} quantity={count}"
transport: modbus_tcp
port: 502
params:
- name: start
type: integer
- name: count
type: integer
- id: modbus_read_holding_registers
label: Modbus Read Holding Registers (function 0x03)
kind: query
command: "MODBUS/TCP function=0x03 address={start} quantity={count}"
transport: modbus_tcp
port: 502
params:
- name: start
type: integer
- name: count
type: integer
description: Must be divisible by 2 for 32-bit pairs
- id: modbus_write_single_coil
label: Modbus Write Single Coil (function 0x05)
kind: action
command: "MODBUS/TCP function=0x05 address={addr} value={0x00|0xFF}"
transport: modbus_tcp
port: 502
params:
- name: addr
type: integer
- name: value
type: integer
description: 0x00 = Off, 0xFF = On (per source 2.1.7)
- id: modbus_write_multiple_coils
label: Modbus Write Multiple Coils (function 0x0F)
kind: action
command: "MODBUS/TCP function=0x0F address={start} quantity={count} bytes={0x0000..0xFFFF}"
transport: modbus_tcp
port: 502
params:
- name: start
type: integer
- name: count
type: integer
- name: bytes
type: integer
description: Output bit pattern (0x0000 = all off, 0xFFFF = all on, 0xF0 = off outputs 1-4 / on 5-8)
- id: modbus_write_multiple_registers
label: Modbus Write Multiple Registers (function 0x10)
kind: action
command: "MODBUS/TCP function=0x10 address={start} quantity={count} values={IEEE754-pair}"
transport: modbus_tcp
port: 502
params:
- name: start
type: integer
- name: count
type: integer
description: Must be even (pairs of 32-bit values)
- name: values
type: string
description: IEEE 754 floats; endianness per Advanced Network config (example: 81.25 -> 0x800042A2 little-endian, 0x42A2_8000 big-endian)
# SNMP PDUs (community = "webrelay" default for v1/v2c; v3 uses USM).
- id: snmp_get
label: SNMP GetRequest
kind: query
command: "SNMP GET OID={oid} version={v1|v2c|v3}"
transport: snmp
params:
- name: oid
type: string
description: e.g. system.sysDescr / sysObjectID / sysUpTime / sysName
- name: version
type: string
- id: snmp_set
label: SNMP SetRequest
kind: action
command: "SNMP SET OID={oid} value={value} version={v1|v2c|v3}"
transport: snmp
params:
- name: oid
type: string
- name: value
type: string
- name: version
type: string
- id: snmp_trap
label: SNMP Trap (configured action)
kind: action
command: "SNMP TRAP condition={relay|threshold|vin} version={v1|v2c|v3}"
transport: snmp
params:
- name: condition
type: string
description: Trigger: relay state change, sensor threshold, supply voltage out of range. Configured as Conditional/Scheduled task action.
- name: version
type: string
description: Notifications (with ack) require v2c or v3.
# MQTT publish tokens. Source documents publish payload template with token substitution.
- id: mqtt_publish
label: MQTT Publish payload with tokens
kind: action
command: "MQTT PUBLISH topic={topic} payload={token-string}"
transport: mqtt
params:
- name: topic
type: string
- name: tokens
type: string
description: Payload tokens from section 4.1.4 table (mac, ver, ser, uptime, ip, port, httpsport, dateTime, name, model, clientID, digitalInput1..4, relay1..4, vin, register1)
- id: mqtt_subscribe
label: MQTT Subscribe
kind: kind_subscribe # error: see below; treated as action for spec purposes
kind: action
command: "MQTT SUBSCRIBE topic={topic}"
transport: mqtt
params:
- name: topic
type: string
# Remote Services (device-initiated TCP connection to external server)
- id: remote_services_connect
label: Remote Services connect
kind: action
command: "TCP connect -> external server sends 'ACK' within 10s; device replies with state.xml"
transport: tcp
params: []
# ControlByWeb Cloud DAT URL set (no port forwarding required)
- id: cloud_state_read
label: Cloud DAT URL state read
kind: query
command: "GET https://api.controlbyweb.cloud/{dat-url}/state.json HTTP/1.1\r\n\r\n"
transport: http
params:
- name: dat-url
type: string
description: Generated per-device DAT URL
- id: cloud_relay_set
label: Cloud DAT URL relay set
kind: action
command: "GET https://api.controlbyweb.cloud/{dat-url}/state.json?relay1=1&relay2=1 HTTP/1.1\r\n\r\n"
transport: http
params:
- name: dat-url
type: string
Feedbacks
- id: relay_state
type: enum
values: [0, 1, 2]
description: Per source: 0=off, 1=on, 2=pulse-active. Returned via state.xml/json and Modbus coil read (0x01).
- id: digital_input_state
type: enum
values: [0, 1]
description: 0=off (voltage not applied), 1=on. Returned via digitalInputX/digitalIOX tags and Modbus function 0x02.
- id: analog_input_value
type: number
description: Float value of analogInputX. Returned via state.xml/json and Modbus function 0x03 (32-bit IEEE 754, little- or big-endian per setup).
- id: vin
type: number
description: Scaled internal Vin measurement.
- id: register_value
type: number
description: Value of registerX (settable via registerX=, counterX=, onTimeX=, totalOnTimeX=; also read).
- id: one_wire_sensor_value
type: number
description: e.g. 77.3; "x.x" sentinel indicates sensor read failure.
- id: utc_time
type: integer
description: Seconds since 1970-01-01 UTC.
- id: serial_number
type: string
description: MAC-like serial "00:0C:C8:00:00:00" format.
- id: syslog_entry
type: string
description: "MM/DD/YYYY HH:MM:SS, (category): (message)" per syslog.txt format.
- id: snmp_sys_uptime
type: string
description: system.sysUpTime - hundredths of seconds since last power.
- id: snmp_sys_descr
type: string
description: system.sysDescr - "X-4xx".
- id: remote_services_ack
type: string
description: 3-character "ACK" reply expected to every connection string within 10s.
Variables
- id: register_X
description: User-writable numeric register (state.xml/json/customState). Writable via HTTP GET registerX=value and Modbus function 0x10.
- id: counter_X
description: User-writable numeric counter (countX=value).
- id: onTime_X
description: Reset-able per-input on time (onTimeX=seconds).
- id: totalOnTime_X
description: Reset-able cumulative on time (totalOnTimeX=seconds).
- id: pulseTime_X
description: One-shot pulse duration override (pulseTimeX=seconds; must precede relayX=2 in query string).
- id: pulse_duration
description: Configured pulse duration (setup page); used by relayX=2 when no pulseTimeX supplied (default example 1.5s).
- id: http_port
description: Configurable web server port (default 80; example shows 8000 when changed).
- id: modbus_tcp_port
description: Modbus/TCP listening port (default 502, configurable in Advanced Network).
- id: endianness
description: IEEE 754 byte order for Modbus register floats (little- or big-endian, per Advanced Network config).
- id: mqtt_topic
description: Publish/subscribe topic configured under Broker tab.
- id: dat_url
description: Per-device ControlByWeb Cloud DAT URL.
Events
- id: snmp_trap_relay_change
description: SNMP trap when relay state changes (configured Conditional/Scheduled action).
- id: snmp_trap_sensor_threshold
description: SNMP trap when configured sensor threshold reached.
- id: snmp_trap_vin_range
description: SNMP trap when supply voltage leaves desired range.
- id: remote_services_state_push
description: "On logic event with action 'send state', device pushes state.xml to the open external connection."
Macros
# UNRESOLVED: source does not document user-facing multi-step macros. Conditional/Scheduled
# task actions exist (source 3.1.3) but command-level recipe is per-task and not enumerated.
Safety
confirmation_required_for: []
interlocks: []
# UNRESOLVED: source contains no safety warnings or interlocks. Modbus/TCP is automatically
# disabled when User account is enabled (because Modbus has no password mechanism) - note only.
Notes
- Source is the ControlByWeb integration manual covering 400/X-600 Series modules broadly; "Quick Connect" is the entity name but specific model hardware details are not enumerated.
- HTTP default port is 80 per convention; example shows port 8000 when changed. Do not assume other ports.
- Modbus/TCP port is explicitly 502 in source (configurable).
- HTTP Basic auth example uses
Authorization: Basicwith Base64("name:password"). Default example creds are "none:webrelay" —webrelayis also the default SNMP v1/v2c community string. pulseTimeXMUST precederelayX=2in the URL query string (source explicit note).- Modbus idle connections close after 50 seconds; send periodic read to keep open. Up to 2 concurrent Modbus/TCP sockets.
- Modbus error responses: function code | 0x80, then exception byte (0x01 unsupported, 0x02 address/qty invalid, 0x03 padding/value out of range).
- Remote Services connection strings expect 3-character "ACK" reply within 10s or device closes.
- MQTT 3.1.1 with Sparkplug B option. Sparkplug B uses defined topic/payload structure (not detailed in source).
- Cloud DAT URL version 2.0 reserved for ControlByWeb.Cloud; do not use for other purposes.
Provenance
source_domains:
- controlbyweb.com
source_urls:
- https://controlbyweb.com/wp-content/uploads/2025/05/cbw-integration-and-protocols-manual.pdf
- https://www.controlbyweb.com/support/cbw-integration-manual/
- https://www.controlbyweb.com/open-api/
retrieved_at: 2026-06-30T15:21:54.724Z
last_checked_at: 2026-07-07T11:09:19.751Z
Verification Summary
verdict: verified
checked_at: 2026-07-07T11:09:19.751Z
matched_actions: 32
action_count: 32
confidence: medium
summary: "All 32 spec actions matched verbatim against source documentation; transport parameters (HTTP port 80, Modbus port 502, Basic auth) confirmed; complete bidirectional coverage of command set. (4 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "source document is a generic 400/X-600 Series integration guide rather than a model-specific manual. Concrete Quick Connect model number not stated. Command set described applies to generically configured I/O; per-channel counts depend on installed I/O."
- "source does not document user-facing multi-step macros. Conditional/Scheduled"
- "source contains no safety warnings or interlocks. Modbus/TCP is automatically"
- "source spec is generic to 400/X-600 Series; concrete Quick Connect I/O count, voltage ratings, and model-specific firmware not stated. Field-by-field population strictly from stated source text only."