Summary
The Clipsal 5500PACA (Pascal Automation Controller) attaches to a C-Bus network via the C-Bus Serial Interface, an RS-232 gateway that converts the C-Bus protocol to/from asynchronous serial. This spec is built from the C-Bus Serial Interface User Guide (CBUS-SIUG Issue 1.17, 9 Dec 2008), which documents the protocol used by the PC Interface (5100PC, 5500PC) and C-Bus SIM (5000SM, 5000SM/2). Control surface covers Point-to-Point (CAL) device management, Point-to-Multi-Point (SAL) Lighting Application commands, status polling, and Serial Interface option/parameter configuration.
Transport
protocols:
- serial
serial:
baud_rate: 9600 # default factory value; selector param $3D allows 9600/4800/2400/1200/600/300
data_bits: null # UNRESOLVED: data bits not stated in source
parity: null # UNRESOLVED: parity not stated in source
stop_bits: null # UNRESOLVED: stop bits not stated in source
flow_control: null # UNRESOLVED: flow control framing not stated; XON/XOFF is a configurable Serial Interface option (Interface Options 1 bit 2), not RS-232 hardware flow control
auth:
type: none # inferred: no auth procedure in source
Traits
traits:
- queryable # inferred: Status Requests, IDENTIFY, RECALL, GETSTATUS queries documented
- levelable # inferred: RAMP to LEVEL lighting commands documented
- routable # inferred: Point-to-Point, Point-to-Multi-Point, Point-to-Point-to-Multi-Point routing documented
Actions
# All payloads verbatim from CBUS-SIUG Issue 1.17. Lighting SAL commands are
# transported inside a Point-to-Multi-Point frame: leading "\" + header ($05) +
# application ($38) + SAL Data + optional checksum + <cr>. The `command:` field
# below shows the SAL Data opcode portion verbatim; full frame assembly is the
# integrator's responsibility per sections 4.2.9.2 and 6.4.
# Checksum is appended only when the SRCHK option (param $30 bit 3) is set.
# --- Special characters / Serial Interface control (section 4.2) ---
- id: si_reset
label: Reset to BASIC Mode
kind: action
command: "~"
params: []
notes: Cancels all options, switches to BASIC Mode. May be followed by <cr>.
- id: si_cancel
label: Cancel Input Buffer
kind: action
command: "?"
params: []
notes: Clears all characters entered since the last "?" or <cr>.
- id: si_smart_connect_shortcut
label: SMART Mode + CONNECT Shortcut
kind: action
command: "|"
params: []
notes: Enters SMART Mode and sets CONNECT option. Discouraged; send before and after <cr>.
- id: si_direct_command_access
label: Direct CAL Command Access Prefix
kind: action
command: "@"
params: []
notes: Prefix sending a Device Management (CAL) command directly to the Serial Interface, bypassing addressing. Preserves modes/options.
# --- Lighting Application SAL commands (section 6.3) ---
# Application Address $38 (standard C-Bus Lighting Application).
- id: light_off
label: Lighting OFF
kind: action
command: "01" # SAL opcode $01; full frame e.g. \0538000108BA -> OFF on Group $08
params:
- name: group
type: integer
description: Group Address Variable number (0-255) to set to 0.
- id: light_on
label: Lighting ON
kind: action
command: "79" # SAL opcode $79
params:
- name: group
type: integer
description: Group Address Variable number (0-255) to set to 255.
- id: light_ramp_instant
label: Ramp to Level - Instantaneous
kind: action
command: "02" # SAL opcode $02; ramp rate instantaneous
params:
- name: group
type: integer
description: Group Address Variable number to ramp.
- name: level
type: integer
description: Target level (0-255) at completion.
- id: light_ramp_4s
label: Ramp to Level - 4 second
kind: action
command: "0A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_8s
label: Ramp to Level - 8 second
kind: action
command: "12"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_12s
label: Ramp to Level - 12 second
kind: action
command: "1A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_20s
label: Ramp to Level - 20 second
kind: action
command: "22"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_30s
label: Ramp to Level - 30 second
kind: action
command: "2A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_40s
label: Ramp to Level - 40 second
kind: action
command: "32"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_1m
label: Ramp to Level - 1 minute
kind: action
command: "3A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_1p5m
label: Ramp to Level - 1.5 minute
kind: action
command: "42"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_2m
label: Ramp to Level - 2 minute
kind: action
command: "4A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_3m
label: Ramp to Level - 3 minute
kind: action
command: "52"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_5m
label: Ramp to Level - 5 minute
kind: action
command: "5A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_7m
label: Ramp to Level - 7 minute
kind: action
command: "62"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_10m
label: Ramp to Level - 10 minute
kind: action
command: "6A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_15m
label: Ramp to Level - 15 minute
kind: action
command: "72"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_ramp_17m
label: Ramp to Level - 17 minute
kind: action
command: "7A"
params:
- name: group
type: integer
- name: level
type: integer
- id: light_terminate_ramp
label: Terminate Ramp
kind: action
command: "09"
params:
- name: group
type: integer
description: Group Address Variable number whose in-progress ramp should be terminated.
# --- Status Requests (section 4.2.9.2) ---
# Issued as a Point-to-Multi-Point command to Application $FF with a trailing
# Status Request block. Example full frame: \05FF007A38004A
- id: status_request_binary
label: Binary Status Request
kind: query
command: "7A" # leading byte of the Status Request block; full SAL Data = "FF 00 7A <application> <start-block>"
params:
- name: application
type: integer
description: Application address to poll (e.g. $38 Lighting).
- name: start_block
type: integer
description: Starting block byte ($00, $20, $40, $60, $80, $A0, $C0, $E0).
notes: Reports Binary State (ON/OFF/ERROR) of GAVs. 32 GAVs per request.
- id: status_request_binary_alt
label: Binary Status Request (legacy FA form)
kind: query
command: "FA" # legacy alternative to $7A
params:
- name: application
type: integer
- name: start_block
type: integer
notes: Discouraged; support may be removed. Prefer $7A form.
- id: status_request_level
label: Level Status Request
kind: query
command: "7307" # SAL Data = "FF 00 73 07 <application> <start-block>"
params:
- name: application
type: integer
- name: start_block
type: integer
notes: Reports dimming Level of 32 GAVs. Serial Interface v4.0.00+ only.
# --- CAL Device/Network Management commands (section 7.1) ---
# Transported as Point-to-Point (CAL) frames, e.g. \0603002102D4
- id: cal_reset
label: CAL Reset
kind: action
command: "08"
params: []
notes: Resets errors latched in a unit.
- id: cal_recall
label: CAL Recall
kind: query
command: "1A"
params:
- name: param_no
type: integer
description: Parameter number at which recall starts.
- name: count
type: integer
description: Bytes to return (1-16, decreases by 1 per bridge).
- id: cal_identify
label: CAL Identify
kind: query
command: "21"
params:
- name: attribute
type: integer
description: Identify attribute number ($00-$11, see IDENTIFY attributes list).
- id: cal_getstatus
label: CAL GetStatus
kind: query
command: "2A"
params:
- name: param_no
type: integer
description: RAM location at which extraction starts.
- name: count
type: integer
description: Bytes to return (1-16). GETSTATUS 0,1 returns unit error status.
# --- IDENTIFY attributes (section 7.2) ---
# Each is a distinct row in the source table. Attribute is the second byte of an
# IDENTIFY ($21) CAL request, e.g. \0605002102 queries attribute $02.
- id: identify_manufacturer
label: Identify Attribute $00 - Manufacturer
kind: query
command: "2100"
params: []
notes: Returns 8 ASCII bytes of manufacturer name.
- id: identify_type
label: Identify Attribute $01 - Type
kind: query
command: "2101"
params: []
notes: Returns 8 ASCII bytes of unit type.
- id: identify_firmware_version
label: Identify Attribute $02 - Firmware Version
kind: query
command: "2102"
params: []
notes: Returns 8 ASCII bytes of firmware version.
- id: identify_summary
label: Identify Attribute $03 - Summary
kind: query
command: "2103"
params: []
notes: Returns part name (6 ASCII), service type, version.
- id: identify_extended_diag
label: Identify Attribute $04 - Extended Diagnostic Summary
kind: query
command: "2104"
params: []
notes: Applications supported, area, CRC, serial, network voltage, common status, error flags.
- id: identify_network_terminal_levels
label: Identify Attribute $05 - Network Terminal Levels
kind: query
command: "2105"
params: []
notes: Output units only. Terminal values after logic.
- id: identify_terminal_levels
label: Identify Attribute $06 - Terminal Levels
kind: query
command: "2106"
params: []
notes: Output units only. Terminal values after logic and local inputs.
- id: identify_network_voltage
label: Identify Attribute $07 - Network Voltage
kind: query
command: "2107"
params: []
notes: Returns ASCII volts e.g. "32.5V".
- id: identify_gav_current
label: Identify Attribute $08 - GAV Values Current
kind: query
command: "2108"
params: []
notes: 16 bytes of current GAV values on network.
- id: identify_gav_stored
label: Identify Attribute $09 - GAV Values Stored
kind: query
command: "2109"
params: []
notes: Output units only. 16 bytes of GAV values stored in EEPROM.
- id: identify_gav_physical
label: Identify Attribute $0A - GAV Physical Addresses
kind: query
command: "210A"
params: []
notes: 16 bytes of GAV physical addresses on network.
- id: identify_logic_assignment
label: Identify Attribute $0B - Logic Assignment
kind: query
command: "210B"
params: []
notes: Output units only. Bit assignment of logic allocation per terminal.
- id: identify_delays
label: Identify Attribute $0C - Delays
kind: query
command: "210C"
params: []
notes: Output units only. Power-up delays per terminal; re-strike delay for relay units.
- id: identify_min_levels
label: Identify Attribute $0D - Minimum Levels
kind: query
command: "210D"
params: []
notes: Output units only. Minimum terminal levels or relay turn-on thresholds.
- id: identify_max_levels
label: Identify Attribute $0E - Maximum Levels
kind: query
command: "210E"
params: []
notes: Output units only. Maximum terminal levels (unused bytes $FF).
- id: identify_current_sense
label: Identify Attribute $0F - Current Sense Levels
kind: query
command: "210F"
params: []
notes: Output units only. Raw A/D current sense values.
- id: identify_output_unit_summary
label: Identify Attribute $10 - Output Unit Summary
kind: query
command: "2110"
params: []
notes: Output units only. Flags byte, GAV STORE enable, mains-recovery time.
- id: identify_dsi_status
label: Identify Attribute $11 - DSI Status
kind: query
command: "2111"
params: []
notes: DSI output units only. Per-channel status, unit status, dimming uC revision.
# --- Parameter set commands (section 10.2) ---
- id: set_parameter_preferred
label: Set Parameter (Preferred Method)
kind: action
command: "@A3{pp}00{vv}"
params:
- name: pp
type: integer
description: Parameter number (hex byte).
- name: vv
type: integer
description: Value to set (hex byte).
notes: Append checksum byte when SRCHK on: "@A3{pp}00{vv}{cc}".
- id: set_parameter_obsolete
label: Set Parameter (Obsolete BASIC-Mode Method)
kind: action
command: "A3{pp}00{vv}"
params:
- name: pp
type: integer
- name: vv
type: integer
notes: BASIC Mode only; issue "~" first.
# --- Addressable parameters (section 10.3) ---
# Each row of the parameter table documented in the source.
- id: set_param_application_address_1
label: Set Parameter $21 - Application Address 1
kind: action
command: "@A32100{vv}"
params:
- name: vv
type: integer
description: Application address $00-$FE; $FF = wildcard.
notes: Unlock required from C-Bus port. Default $FF.
- id: set_param_application_address_2
label: Set Parameter $22 - Application Address 2
kind: action
command: "@A32200{vv}"
params:
- name: vv
type: integer
description: Application address $00-$FE; $FF = unused.
notes: Unlock required from C-Bus port. Default $FF.
- id: set_param_interface_options_1
label: Set Parameter $30 - Interface Options 1
kind: action
command: "@A33000{vv}"
params:
- name: vv
type: integer
description: 8-bit options (bits: CONNECT, XONXOFF, SRCHK, SMART, MONITOR, IDMON).
notes: Volatile. Serial port write only. Loaded from $41 on power-up.
- id: set_param_baud_rate
label: Set Parameter $3D - Baud Rate Selector
kind: action
command: "@A33D00{vv}"
params:
- name: vv
type: integer
description: "$01=4800, $02=2400, $03=1200, $04=600, $05=300, any other=9600."
notes: Serial port write only. Default $FF (9600).
- id: set_param_interface_options_2
label: Set Parameter $3E - Interface Options 2
kind: action
command: "@A33E00{vv}"
params:
- name: vv
type: integer
description: C-Bus options (CLOCK GEN, BURDEN).
notes: Normally set by C-Bus installation software. Default $00.
- id: set_param_interface_options_1_powerup
label: Set Parameter $41 - Interface Options 1 Power Up Settings
kind: action
command: "@A34100{vv}"
params:
- name: vv
type: integer
description: Mirrors Interface Options 1 ($30); copied to $30 on power-up.
notes: Unlock required from C-Bus port. Default $00.
- id: set_param_interface_options_3
label: Set Parameter $42 - Interface Options 3
kind: action
command: "@A34200{vv}"
params:
- name: vv
type: integer
description: Bits: PCN, LOCAL_SAL, PUN, EXSTAT.
notes: Unlock required from C-Bus port. Default $00.
# Parameters $EB-$F2 (Custom Manufacturer), $F3-$F6 (Serial Number), $F7-$FE
# (Custom Type) are read-only and therefore not exposed as set actions.
# --- Baud-rate auto-set sequence (section 10.3.3) ---
- id: baud_autoset_9600
label: Force 9600 Baud on Power-Up
kind: action
command: "\\0"
params: []
notes: Send the two ASCII characters '\' ($5C) and '0' ($30) at 9600 baud within 5 s of power application.
Feedbacks
# Reply formats emitted by the Serial Interface (section 4.3).
- id: cal_reply_short
type: string
description: Short-form CAL Reply (BASIC Mode). CAL Data + checksum.
- id: cal_reply_long
type: string
description: Long-form CAL Reply (SMART Mode). Includes Unit Address, Serial Interface Unit Address, Network.
- id: monitored_sal
type: string
description: Unsolicited SAL message observed on C-Bus when CONNECT option set. Short form in BASIC Mode, long form in SMART Mode.
- id: confirmation_ok
type: enum
values: ["."]
description: Alpha followed by "." means command transmitted to C-Bus successfully.
- id: confirmation_fail_no_ack
type: enum
values: ["#"]
description: Alpha followed by "#" - too many retransmissions, no acknowledge.
- id: confirmation_fail_corrupt
type: enum
values: ["$"]
description: Alpha followed by "$" - corruption during transmission.
- id: confirmation_fail_clock
type: enum
values: ["%"]
description: Alpha followed by "%" - lost C-Bus synchronising clock.
- id: confirmation_input_too_long
type: enum
values: ["'"]
description: Single-quote means received character sequence too long.
- id: power_up_notify
type: enum
values: ["+"]
description: "++<cr><lf>" emitted after init when PUN option set. First "+" may be corrupt/missing.
- id: parameter_change_notify
type: enum
values: ["="]
description: "==<cr><lf>" emitted when internal parameter updated over C-Bus, if PCN option set.
- id: input_error
type: enum
values: ["!"]
description: "!" returned when PCI cannot accept supplied data (checksum fail, buffer full).
- id: status_reply_standard
type: string
description: Standard Format Status Reply; Status Header "C0"+count, application, block start, 2-bit-per-GAV status bytes. Returned over >=3 lines.
- id: status_reply_extended
type: string
description: Extended Format Status Reply; Status Header "E0"+count, coding byte, application, block start, status bytes. Returned for Level Status Request, or Switched Status Request when EXSTAT option on.
- id: acknowledge_reply
type: string
description: ACKNOWLEDGE CAL reply ($32 + Param No + Code), returned in response to parameter set commands.
- id: reply_command
type: string
description: REPLY CAL command ($80 + count + Param No + bytes), returned in response to RECALL/IDENTIFY/GETSTATUS.
Variables
# Settable parameters exposed as variables (current value queryable via RECALL).
# Population from section 10.3 parameter table.
- name: application_address_1
param_no: "21"
type: byte
access: read_write
default: "FF"
- name: application_address_2
param_no: "22"
type: byte
access: read_write
default: "FF"
- name: interface_options_1
param_no: "30"
type: byte
access: read_write
default: "00"
volatile: true
- name: baud_rate_selector
param_no: "3D"
type: byte
access: read_write
default: "FF"
- name: interface_options_2
param_no: "3E"
type: byte
access: read_write
default: "00"
- name: interface_options_1_powerup
param_no: "41"
type: byte
access: read_write
default: "00"
- name: interface_options_3
param_no: "42"
type: byte
access: read_write
default: "00"
# Read-only variables (section 10.3.7-10.3.9)
- name: custom_manufacturer
param_no_range: "EB-F2"
type: string
access: read_only
- name: serial_number
param_no_range: "F3-F6"
type: bytes
access: read_only
- name: custom_type
param_no_range: "F7-FE"
type: string
access: read_only
Events
# Unsolicited notifications emitted by the Serial Interface.
# - Power Up Notification (PUN) and Parameter Change Notification (PCN) are
# already enumerated in Feedbacks above as `power_up_notify` and
# `parameter_change_notify`.
# - Monitored SAL and Status Replies when CONNECT/MONITOR options set are also
# in Feedbacks.
# UNRESOLVED: no other unsolicited event classes documented in source.
Macros
# Multi-step sequences documented verbatim in source examples (section 9).
- id: macro_set_smart_srchk_connect
steps:
- command: "~@A3300019"
notes: Force BASIC Mode, then set Interface Options 1 ($30) to $19 (SMART + SRCHK + CONNECT) via preferred @A3 method (section 9.4).
- id: macro_multiple_lighting_commands
steps:
- command: "\\05380001210122012301240A25010A2601D4r"
notes: Turn groups $21-$24 ON, ramp $25 and $26 to $01 at 4 s rate, request confirmation (section 9.5).
Safety
confirmation_required_for: []
interlocks:
- compound_device_power_sync: "For compound devices (separate control processor power), always set PUN option and re-initialise all Serial Interface settings on PUN receipt (section 5)."
- basic_mode_for_param_set_obsolete: "Obsolete parameter-set method (A3pp00vv) only valid in BASIC Mode; issue '~' first (section 10.2.2)."
- priority_class_1_forbidden: "Use of C-Bus Priority Class 1 is forbidden without prior Clipsal approval (section 3.4)."
- status_request_rate: "Excessive Status Requests dramatically degrade network performance; poll infrequently and cache local state (section 4.2.9.2)."
- burden_change_double_write: "Changes to Interface Options 2 BURDEN bit must be issued twice within 10 s to take effect (section 10.3.4)."
# No electrical/voltage safety interlocks stated in this source document.
Notes
- Source document is CBUS-SIUG Issue 1.17 (9 Dec 2008) — C-Bus Serial Interface & C-Bus Development Kit — describing Serial Interface version 4.0.00 and higher. It covers the protocol used by 5100PC, 5500PC, 5000SM, 5000SM/2 PC Interface / SIM devices.
- The 5500PACA (Pascal Automation Controller) is the target product per input metadata but is not explicitly named in the refined source document; coverage of the 5500PACA's Pascal/PICED programming interface, physical RS-232 pinout, voltage, and current ratings is out of scope of this source.
- All commands sent to the Serial Interface terminate with
<cr>($0D); max 45 characters between leading\and<cr>(section 4.2.2). - All Serial Interface checksums are 2's-complement mod-256 sums of the preceding hex byte pairs; appended only when SRCHK option set (section 3.6).
- Default baud rate is 9600; lower rates (4800/2400/1200/600/300) selectable via param $3D but not recommended due to limited internal buffering (section 10.3.3).
- Serial Interface firmware <3.11 is pre-release; v3 firmware ≤3.16 has a baud-reversion bug limiting those units to 9600 baud (section 11).
- Default factory Interface Options 1 ($30) value is $00 (BASIC Mode, no options).
Spec built. Verbatim payload from CBUS-SIUG Issue 1.17. Enumerated: 4 special chars, 16 ramp opcodes + ON/OFF/TERMINATE, 2 status requests + legacy FA, 4 CAL commands, 18 IDENTIFY attrs ($00-$11), 2 param-set methods, 7 settable params, autoset, 9 reply types, read-only params noted omitted. Safety from section 5/3.4/4.2.9.2/10.3.4/10.2.2.
## Provenance
```yaml
source_domains:
- web.archive.org
- noushouse.com.au
- updates.clipsal.com
- cleverhome.com.au
- manualshelf.com
source_urls:
- "https://web.archive.org/web/20180205062541if_/http://training.clipsal.com/downloads/OpenCBus/Serial%20Interface%20User%20Guide.pdf"
- "https://www.noushouse.com.au/brochures/Clipsal/System%20Units/Clipsal-C-Bus-5500PACA-Pascal-Automation-Controller.pdf"
- https://updates.clipsal.com/ClipsalSoftwareDownload/mainsite/cis/technical/AutoController/LSS5500NAC_LSS5500SHAC_FW_v1.0_EN.pdf
- https://www.cleverhome.com.au/manuals/Clipsal-C-Bus-5500PACA-Pascal-Automation-Controller-Installation.pdf
- https://www.manualshelf.com/manual/clipsal/c-bus/user-guide-english.html
retrieved_at: 2026-07-26T06:52:29.843Z
last_checked_at: 2026-08-05T08:14:27.946Z
```
## Verification Summary
```yaml
verdict: verified
checked_at: 2026-08-05T08:14:27.946Z
matched_actions: 58
action_count: 58
confidence: medium
summary: "All 58 spec actions map 1:1 to SAL opcodes (6.3), CAL commands (7.1), IDENTIFY attrs $00-$11 (7.2), and parameter methods (10.2/10.3) in the source. (12 unresolved item(s) noted in Known Gaps.)"
```
## Known Gaps
```yaml
- "The 5500PACA is named only in the input metadata; the refined source document covers the C-Bus Serial Interface protocol generically and does not explicitly mention the 5500PACA model. Voltage/current/power specs, physical wiring, and PICED/Pascal programming interface are out of scope of this source."
- "data bits not stated in source"
- "parity not stated in source"
- "stop bits not stated in source"
- "flow control framing not stated; XON/XOFF is a configurable Serial Interface option (Interface Options 1 bit 2), not RS-232 hardware flow control"
- "no other unsolicited event classes documented in source."
- "5500PACA model not explicitly named in source; relationship of this protocol guide to the 5500PACA's primary programmable interface is unconfirmed."
- "serial data bits, parity, stop bits, hardware flow control not stated in source."
- "physical connector pinout, voltage, current, power specs not stated in source."
- "firmware version compatibility range for 5500PACA not stated."
- "full CAL command catalogue (unit-specific commands \"subject to change without notice\" per section 7) — only the common subset tabulated in section 7.1 is enumerated here."
- "non-Lighting C-Bus Applications (CBUS-APP document set) not in source; only the Lighting Application $38 SAL subset is enumerated."
```
---