Summary
APC Switched Rack PDU with CLI control via Telnet, SSH v1/v2, or serial RS-232. Supports outlet-level power control (on/off/reboot), user management, power monitoring, and configuration of delays, thresholds, and alarms. Authentication via username/password required.
Transport
protocols:
- tcp # inferred: Telnet and SSH explicitly listed, both run over TCP
- serial
addressing:
port: null # UNRESOLVED: port number not stated in source
serial:
baud_rate: 9600 # stated: "Serial default baud rate: 9600"
data_bits: null # UNRESOLVED: data bits not stated in source
parity: null # UNRESOLVED: parity not stated in source
stop_bits: null # UNRESOLVED: stop bits not stated in source
flow_control: null # UNRESOLVED: flow control not stated in source
auth:
type: credentialed # stated: login requires username + password
Traits
- powerable # on/off/reboot commands present
- routable # outletgroups command present
- queryable # status, current, power, ver commands present
- levelable # powerondelay, poweroffdelay, rebootduration, lowloadwarning, nearoverloadwarning, overloadalarm, overloadrestriction commands present
Actions
- id: off
label: Turn Outlet Off
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet name or number, or "all"
- type: string
description: Range "start-end"
description: Outlet(s) to turn off
example: "off 1,5-7"
- id: on
label: Turn Outlet On
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet name or number, or "all"
- type: string
description: Range "start-end"
description: Outlet(s) to turn on
example: "on 1,5-7"
- id: reboot
label: Reboot Outlet
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet name or number, or "all"
- type: string
description: Range "start-end"
description: Outlet(s) to reboot
example: "reboot 1,5-7"
- id: powerondelay
label: Set Power-On Delay
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet name or number
- type: string
description: Range "start-end"
- name: time
type: union
variants:
- type: integer
description: Delay in seconds
- type: string
description: "never" to keep outlet off
example: "powerondelay 1 5"
- id: poweroffdelay
label: Set Power-Off Delay
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet name or number
- type: string
description: Range "start-end"
- name: time
type: union
variants:
- type: integer
description: Delay in seconds
- type: string
description: "never" to keep outlet on
example: "poweroffdelay 1 3"
- id: rebootduration
label: Set Reboot Duration
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet name or number
- type: string
description: Range "start-end"
- name: time
type: integer
description: Seconds outlet remains off before restarting
example: "rebootduration 1 10"
- id: adduser
label: Add User
kind: action
params:
- name: user_name
type: string
description: User name (1-10 printable ASCII characters)
example: "adduser john_reynolds"
- id: deluser
label: Delete User
kind: action
params:
- name: user_name
type: string
description: User name (1-10 printable ASCII characters)
example: "deluser john_reynolds"
- id: assign
label: Assign Outlets to User
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet number or name
- type: string
description: Range "start-end"
- name: user_name
type: string
description: User name
example: "assign 1-3,5,7 john_reynolds"
- id: unassign
label: Unassign Outlets from User
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet number or name
- type: string
description: Range "start-end"
- name: user_name
type: string
description: User name
example: "unassign 1-3,5,7 john_reynolds"
- id: passwd
label: Change Password
kind: action
params:
- name: user_name
type: string
description: Optional user name (administrator can change other user's password)
example: "passwd john_reynolds"
- id: name
label: Name Outlet or PDU
kind: action
params:
- name: outlet
type: union
variants:
- type: string
description: Outlet number, or "master" for PDU system name
- type: string
description: Outlet name
- name: new_name
type: string
description: Name to assign (up to 23 printable ASCII characters)
example: 'name 1 "Web Server"'
- id: lowloadwarning
label: Set Low-Load Warning Threshold
kind: action
params:
- name: phase_number
type: integer
description: Phase number (1, 2, or 3; default 1)
- name: current
type: number
description: Threshold in amps
example: "lowloadwarning 1 5"
- id: nearoverloadwarning
label: Set Near-Overload Warning Threshold
kind: action
params:
- name: phase_number
type: integer
description: Phase number (1, 2, or 3; default 1)
- name: current
type: number
description: Threshold in amps
example: "nearoverloadwarning 1 15"
- id: overloadalarm
label: Set Overload Alarm Threshold
kind: action
params:
- name: phase_number
type: integer
description: Phase number (1, 2, or 3; default 1)
- name: current
type: number
description: Threshold in amps
example: "overloadalarm 1 16"
- id: overloadrestriction
label: Set Overload Restriction
kind: action
params:
- name: phase_number
type: integer
description: Phase number (1, 2, or 3; default 1)
- name: setting
type: string
description: "on" or "off"
example: "overloadrestriction 1 on"
- id: pducoldstartdelay
label: Set PDU Cold-Start Delay
kind: action
params:
- name: time
type: union
variants:
- type: integer
description: Delay in seconds (0-300)
- type: string
description: "never" to keep outlets off until explicitly turned on
example: "pducoldstartdelay 30"
- id: reset_defaults_pdu
label: Reset PDU to Defaults
kind: action
params: []
example: "reset_defaults_pdu"
- id: uploadini
label: Upload INI File
kind: action
params: []
description: Upload INI file via XMODEM-CRC over serial connection
example: "uploadini"
- id: exit
label: Exit CLI
kind: action
params: []
description: Exit CLI session (alias: logout, logoff, quit, bye)
example: "exit"
- id: help
label: Help
kind: action
params:
- name: command
type: string
description: Optional command name for specific help
example: "help"
- id: whoami
label: Show Active User
kind: action
params: []
description: Display the user name of the currently logged-in user.
example: "whoami"
- id: outletgroups
label: List Outlet Groups
kind: action
params: []
description: List the outlet synchronization groups defined on the Switched Rack PDU, including remote PDU members when inter-PDU synchronization is enabled.
example: "outletgroups"
- id: current
label: Read Current Draw
kind: action
params: []
description: Display the total current draw in amps. Single-phase and banked PDUs report a single value; 3-phase PDUs report T1/T2/T3.
example: "current"
- id: list
label: List Users and Outlet Assignments
kind: action
params: []
description: List all users and their assigned outlet numbers. Output varies by caller account type and authentication method (local vs RADIUS).
example: "list"
- id: power
label: Read Total Power Usage
kind: action
params: []
description: Read the total power usage of the Switched Rack PDU in volt-amps and watts.
example: "power"
- id: ver
label: Show Device Info
kind: action
params: []
description: Display firmware version, model number, outlet count, maximum current, and phase configuration of the Switched Rack PDU.
example: "ver"
Feedbacks
- id: status
label: Outlet Status
type: enum
values:
- ON
- OFF
- "ON*" # asterisk = control action pending
- "OFF*"
description: Format "_n_:ON:_name_" or "_n_:OFF:_name_", trailing asterisk indicates pending action
- id: power_state
label: Power State
type: enum
values: [on, off]
- id: power_on_delay
label: Power-On Delay
type: union
variants:
- type: integer
description: Seconds
- type: string
description: "never"
- id: power_off_delay
label: Power-Off Delay
type: union
variants:
- type: integer
description: Seconds
- type: string
description: "never"
- id: reboot_duration
label: Reboot Duration
type: integer
description: Seconds outlet remains off before restarting
- id: current_draw
label: Current Draw
type: union
variants:
- type: number
description: Amps (single-phase/banked)
- type: object
description: 3-phase, keys T1/T2/T3 each with number in amps
- id: total_power
label: Total Power
type: object
properties:
- name: volt_amps
type: number
description: VA
- name: watts
type: number
description: W
- id: device_info
label: Device Information
type: object
properties:
- name: aos_firmware_version
type: string
- name: pdu_firmware_version
type: string
- name: model
type: string
- name: outlet_count
type: integer
- name: max_current
type: number
description: Amps
- name: phase_configuration
type: string
description: Single, Banked, or 3 Phase
- id: user_list
label: User List
type: object
properties:
- name: users
type: array
items:
type: object
properties:
- name: auth_type
type: string
description: "Local" or "Radius"
- name: user
type: string
- name: outlets
type: array
items:
type: integer
- id: outlet_group_list
label: Outlet Group List
type: array
items:
type: object
properties:
- name: group_name
type: string
- name: members
type: array
items:
type: object
properties:
- name: ip_address
type: string
- name: outlets
type: array
items:
type: integer
- id: low_load_warning_threshold
label: Low-Load Warning Threshold
type: object
properties:
- name: phase
type: integer
- name: current
type: number
description: Amps
- id: near_overload_warning_threshold
label: Near-Overload Warning Threshold
type: object
properties:
- name: phase
type: integer
- name: current
type: number
description: Amps
- id: overload_alarm_threshold
label: Overload Alarm Threshold
type: object
properties:
- name: phase
type: integer
- name: current
type: number
description: Amps
- id: overload_restriction
label: Overload Restriction
type: object
properties:
- name: phase
type: integer
- name: setting
type: string
description: "on" or "off"
- id: cold_start_delay
label: PDU Cold-Start Delay
type: union
variants:
- type: integer
description: Seconds
- type: string
description: "never"
- id: error_response
label: CLI Error Response
type: enum
values:
- E100 # Command does not exist
- E101 # Invalid command arguments
- E102 # User already exists
- E103 # User does not exist
- E104 # User does not have access to this command
- E200 # Input error (required input not received within 3 minutes)
Variables
# No distinct Variables section - all settable parameters are exposed via Actions above.
# The status command serves as the primary query mechanism for outlet state.
Events
# UNRESOLVED: no unsolicited event notifications described in source - device sends
# only command responses, no push-style events.
Macros
# UNRESOLVED: no explicit multi-step sequences described as macros in source.
# Synchronized outlet groups (via outletgroups command) enable coordinated multi-outlet
# control but are not documented as named macros.
Safety
confirmation_required_for: []
interlocks:
- description: >-
Overload restriction (overloadrestriction on) prevents outlets from turning on
while the overload alarm threshold is violated. Must be explicitly configured.
- description: >-
Three consecutive failed log-on attempts triggers a 2-minute lockout.
- description: >-
Cold-start delay (pducoldstartdelay never) keeps outlets off after AC power
is applied until explicitly turned on via the on command.
- description: >-
CLI activity auto-logs off after 3 minutes of inactivity (configurable 1-10 minutes).
- description: >-
XMODEM file transfer at non-default baud rate requires resetting baud rate
to 9600 to re-establish communication after transfer completes.
Notes
Serial connection uses default 9600 baud, 8N1 (assumed; data_bits/parity/stop_bits not stated in source). Telnet/SSH port number not stated in source — prior research indicated port 1023 for some models but this was not confirmed in the source document. CLI accepts commands in any capitalization; arguments are case-sensitive. String arguments containing spaces, commas, or semicolons must be enclosed in double quotes. Escape character is backslash only — no standard escape sequences recognized. Inactivity logout default is 3 minutes (range 1-10 minutes configurable).
Provenance
source_domains:
- usermanual.wiki
- ckm-content.se.com
- se.com
source_urls:
- https://usermanual.wiki/Apc/ApcCommandLineInterfaceUsersManual470947.999847818.pdf
- https://ckm-content.se.com/ckmContent/sfc/servlet.shepherd/document/download/0691H00000GejKSQAZ
- https://www.se.com/us/en/product-range/61799-apc-netshelter-switched-rack-pdus/
retrieved_at: 2026-04-29T22:37:54.944Z
last_checked_at: 2026-06-02T21:39:46.372Z
Verification Summary
verdict: verified
checked_at: 2026-06-02T21:39:46.372Z
matched_actions: 27
action_count: 27
confidence: medium
summary: "Full CLI protocol coverage with outlet control, user management, and monitoring commands (9 unresolved item(s) noted in Known Gaps.)"
Known Gaps
- "Telnet/SSH port number not stated in source. UNRESOLVED: TCP port number not stated in source."
- "port number not stated in source"
- "data bits not stated in source"
- "parity not stated in source"
- "stop bits not stated in source"
- "flow control not stated in source"
- "no unsolicited event notifications described in source - device sends"
- "no explicit multi-step sequences described as macros in source."
- "TCP port number not stated in source. UNRESOLVED: SSH version 1 security concerns (source mentions v1 and v2). UNRESOLVED: firmware version compatibility not stated in source."